Chapter 3 – protection functions, Max. no. of protection stages in one applications, Protection functions – Rockwell Automation 865 Differential Protection Relay User Manual
Page 45: General features of protection stages, Setting groups, Chapter

Chapter
3
865-UM001A-EN-P – July 2009
Protection
Functions
Each protection stage can independently be enabled or disabled
according to the requirements of the intended application.
The device limits the maximum number of enabled stages to about
30, depending on the type of the stages. For more information,
please see the configuration instructions in Chapter 2 in the first part
of this manual.
Table 3.1 – List of Protection Functions
IEEE/
ANSI code
IEC Symbol
Function Name
50/51
3I>, 3I>>, 3I’>, 3I’>>
Overcurrent protection
87
∆I>, ∆I>>
Differential overcurrent protection
46 I
2
>, I’
2
> Current
unbalance
protection
49
T>
Thermal overload protection
50N/51N
I
0
>,
I
0
>>,
I
0
>>>,
I
0
>>>>
Earth fault protection
50BF
CBFP
Circuit-breaker failure protection
99 Prg1...8
Programmable
stages
50ARC
50NARC
ArcI>, ArcI’>
ArcI
01
>, ArcI
02
>
Optional arc fault protection
Setting
Groups
Most stages have two setting groups. Changing between setting
groups can be controlled manually or using any of the digital inputs,
virtual inputs, virtual outputs or LED indicator signals. By using
virtual I/O the active setting group can be controlled using the local
panel mimic display, any communication protocol or using the
inbuilt programmable logic functions.
Maximum Number of
Protection Stages
in one application
General Features of
Protection Stages
Protection Functions