Digital inputs – Rockwell Automation 865 Differential Protection Relay User Manual
Page 120
6-2 Control
Functions
865-UM001A-EN-P – July 2009
Digital Inputs
There are 6 digital inputs available for control purposes. The
polarity – normal open (NO) / normal closed (NC – and a delay can
be configured according the application. The signals are available for
the output matrix, block matrix, user's programmable logic etc.
The contacts connected to digital inputs DI1 ... DI6 must be dry
(potential free). These inputs use the common internal 48 Vdc
wetting voltage from terminal X3:1, only.
Table 6.2 – Contact Connection to Digital Inputs
Wetting voltage
Common
input
Input group
On
Off
X7:7
X7: 1-6 (DI 7-12)
≥18 V
DC
or ≥50 V
AC
≤10 V
DC
or
≤5 V
AC
NOTE: These digital inputs must not be connected parallel with
inputs of another device.
Label and description texts can be edited with SetPointPS according
the application. Labels are the short parameter names used on the
local panel and descriptions are the longer names used by
SetPointPS.
Table 6.3 – Parameters of Digital Inputs
Parameter
Value
Unit
Description
Set
DI1 ... DI6
0
1
Status of digital input
DI COUNTERS
DI1 ... DI6
0 ... 65535
Cumulative active edge counter
(Set)
DELAYS FOR DIGITAL INPUTS
DI1 ... DI6
0.00 ... 60.00
s
Definite delay for both on and off
transitions
Set
CONFIGURATION DI1 ... DI6
Inverted no
yes
For normal open contacts (NO).
Active edge is 0
⇒1
For normal closed contacts (NC)
Active edge is 1
⇒0
Set
Alarm display
no
yes
No pop-up display
Alarm pop-up display is activated
at active DI edge
Set
On event
On
Off
Active edge event enabled
Active edge event disabled
Set
Off event
On
Off
Inactive edge event enabled
Inactive edge event disabled
Set
NAMES for DIGITAL INPUTS (editable with SetPointPS only)
Label String
of
max.
10 characters
Short name for DIs on the local
display
Default is "DIn", n=1...6
Set
Description String
of
max.
32 characters
Long name for DIs. Default is
"Digital input n", n=1...6
Set
Set = An editable parameter (password needed)