Rockwell Automation 20-750-CNETC PowerFlex Coaxial ControlNet Option Module User Manual
Page 32
![background image](/manuals/577801/32/background.png)
32
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Chapter 3
Configuring the Option Module
Restoring Option Module
Parameters to Factory
Defaults
As an alternate reset method, you can restore the option module parameters by
using a MEMORY folder menu item instead of using
Device Parameter 07 -
[Reset Module]
described in
Resetting the Option Module on page 31
. The
MEMORY folder method provides two ways to restore the option module
Device and Host parameters:
•
ALL—restores ALL option module
Device and Host parameters to their
factory default values.
•
MOST—restores MOST option module
Device and Host parameters—
except
Device Parameter 05 - [Net Addr Cfg] which is used for network
setup.
Follow these steps to restore option module
Device and Host parameters to their
factory default values.
1.
Access the Status screen, which is displayed on HIM powerup.
2.
Use the
or
key to scroll to the Port in which the option
module is installed.
3.
Press the
key to display its last-viewed folder.
4.
Use the
or
key to scroll to the MEMORY folder.
5.
Use the
or
key to select Set Defaults.
6.
Press the
(Enter) key to display the Set Defaults pop-up box.
7.
Press the
(Enter) key again to display the warning pop-up box to
reset
Device and Host parameters to their factory default values.
8.
Press the MOST
soft key to restore MOST Device and Host parameters to
factory defaults or press the ALL
soft key to restore ALL parameters. Or
press the ESC
soft key to cancel.
9.
Reset the option module using
Device Parameter 07 - [Reset Module] or
by cycling power to the drive so that the restored parameters take effect.
IMPORTANT
When performing a Set Defaults, the drive may detect a conflict and
then not allow this function to occur. If this happens, first resolve the
conflict and then repeat this Set Defaults procedure. Common reasons
for a conflict include the drive running or a controller in Run mode.
00
Stopped
0.00 Hz
AUTO
Host Drive
240V
4.2A
Rev 3.002 Ser. A
ESC
REF
TEXT
F
PAR#