beautypg.com

Rockwell Automation 20-750-CNETC PowerFlex Coaxial ControlNet Option Module User Manual

Page 131

background image

Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012

131

ControlNet Objects

Appendix C

16

Get

Parameter Processing Error USINT

0 = No error
1 = Value is less than the minimum
2 = Value is greater than the maximum

18

Get

International DPI Offline
Parameter Text

Struct of:

STRINGN
STRINGN

International parameter name
International offline units

19

Get

International DPI Online
Parameter Text

Struct of:

STRINGN
STRINGN

International parameter name
International online units

20

Get

International DPI Online
Read Full

Struct of:

BOOL[32]
CONTAINER
CONTAINER
CONTAINER
CONTAINER
UINT
UINT
UINT
UINT
UINT
INT
USINT[3]
USINT
BOOL[32]
STRINGN
STRINGN

Descriptor
Parameter value
Online minimum value
Online maximum value
Online default value
Next
Previous
Multiplier
Divisor
Base
Offset
Link
Pad word (always zero)
Extended descriptor
International parameter name
International online parameter units

21

Get

DPI Extended Descriptor

UDINT

Extended Descriptor (see

page 133

)

22

Get

International DPI Offline
Read Full

Struct of:

BOOL
CONTAINER
CONTAINER
CONTAINER
UINT
UINT
UINT
UINT
UINT
UINT
UINT
USINT
USINT
UINT
UINT
CONTAINER
UINT
UINT
UINT
INT
BOOL[32]
STRINGN
STRINGN

Descriptor
Offline minimum value
Offline maximum value
Offline default value
Online minimum parameter instance
Online maximum parameter instance
Online default parameter instance
Multiplier parameter instance
Divisor parameter instance
Base parameter instance
Offset parameter instance
Formula number
Pad word (always zero)
Help instance
Pad word (always a value of zero)
Parameter value
Multiplier
Divisor
Base
Offset
Extended DPI descriptor
International DPI parameter name
International DPI offline parameter units

(1) A CONTAINER is a 32-bit block of data that contains the data type used by a parameter value. If signed, the value is sign extended. Padding is used in the CONTAINER

to ensure that it is always 32-bits.

(2) This value is used in the formulas used to convert the parameter value between display units and internal units. See

Formulas for Converting on page 134

.

(3) Do NOT continually write parameter data to NVS. See the attention on

page 73

.

Attribute ID

Access Rule Name

Data Type

Description