Setting the fault configuration parameters – Rockwell Automation 20-750-CNETC PowerFlex Coaxial ControlNet Option Module User Manual
Page 30
![background image](/manuals/577801/30/background.png)
30
Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Chapter 3
Configuring the Option Module
Figure 4 - Edit Fault Action HIM Screens
Changes to these parameters take effect immediately. A reset is not required.
If communication is disrupted and then is re-established, the drive will
automatically receive commands over the network again.
Setting the Fault Configuration Parameters
When setting
Host Parameter 33 - [Comm Flt Action], 34 - [Idle Flt Action]
or 36 - [Msg Flt Action] to ‘Send Flt Cfg’, the values in the following parameters
are sent to the drive after a communication fault, idle fault, and/or explicit
messaging for drive control fault occurs. You must set these parameters to values
required by your application.
Changes to these parameters take effect immediately. A reset is not required.
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲
▼
Edit Comm Flt Action
Fault
0
0 << 4
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲
▼
Edit Idle Flt Action
Fault
0
0 << 4
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲
▼
Edit Msg Flt Action
Fault
0
0 << 4
Option Module Host Parameter
Description
Parameter 37 - [Flt Cfg Logic]
A 32-bit value sent to the drive for Logic Command.
Parameter 38 - [Flt Cfg Ref]
A 32-bit REAL (floating point) value sent to the drive for Reference.
Parameter 39 - [Flt Cfg DL 01]
through
Parameter 54 - [Flt Cfg DL 16]
A 32-bit integer value sent to the drive for a Datalink. If the destination of the
Datalink is a REAL (floating point) parameter, you must convert the desired
value to the binary representation of the REAL value. (An internet search of
‘hex to float’ provides a link to a tool to do this conversion.)