Chapter 11
Technical specifications
To meet the requirements of the relevant product standards (e.g., EN 61 496-1), the external voltage supply for
the devices (SELV) must be able to bridge a brief mains failure of 20 ms. Power supplies according to EN 60 204-
1 satisfy this requirement. Suitable power supplies are available as accessories from Rockwell Automation (see
“Accessories” on page 53).
Within the limits of V
s
.
Table 15 - Data sheet SC300
Minimum
Typical
Maximum
Housing
Material
Aluminium die-cast
Dimensions
See “Dimensional drawings” on page 50.
Total weight
0.355 kg
Reflective tape (length × width)
for resolution:
20 mm
1.00 m × 37 mm
24 mm
1.20 m × 37 mm
30 mm
1.50 m × 48 mm
Power-up delay after connecting the
supply voltage
6 s
Electrical data
Supply voltage V
s
at the device (SELV)
19.2V
24V
28.8V
Permissible cable resistance on the supply
cable
1
Ω
Residual ripple
Operating current
at 24V without output load
165 mA
with maximum output load
690 mA
Power consumption
at 24V without output load
4 W
with maximum output load
19 W
Electrical connection
M12
× 8 (see “System connection” on page 28)
Cable length for wire cross-section
0.25 mm²
7.5 m
Synchronization
Electrical (see “System connection” on page 28)
External device monitoring (EDM) input
Resistance HIGH
2 k
Ω
Capacitance
15 nF
Voltage (IEC 61
1312)
HIGH
11 V
24 V
30 V
LOW
–3 V
0 V
5 V
Static current
6 mA
15 mA