Locking the internal teach-in key – Rockwell Automation 442L SC300 Safety Sensor User Manual User Manual
Page 45
Rockwell Automation Publication 10000202762 Ver 00 - January 2012
43
Chapter 8
Configuration
If there is no signal or 0 V on the
external device monitoring (EDM) input, the safety
camera system will deactivate the external device monitoring and save this configuration
in the device.
Check the effectiveness of the protective device as described in “Test notes” on page 38.
Locking the internal teach-in key
In the default delivery status the internal teach-in key is unlocked, i.e. it can be used. To
permit remote teach-in and/or to help protect the configuration, you can connect an
external key-operated pushbutton for teach-in and lock the internal teach-in key.
How to lock the internal teach-in key:
Connect an external key-operated pushbutton for teach-In (“Connecting the SC300” on
page 28).
Switch on the SC300.
Perform a teach-in procedure using the key-operated pushbutton for teach-in.
The SC300 locks the internal teach-in key and saves this configuration in the device.
Teach-in can now only be performed using the key-operated pushbutton for teach-in.
Check the effectiveness of the protective device as described in “Test notes” on page 38.
How to unlock the internal teach-in key:
Switch on the SC300.
Press the key-operated pushbutton for teach-in for at least 60 seconds.
The SC300 unlocks the internal teach-in key and saves this configuration in the device.
If you no longer need the key-operated pushbutton for teach-in, remove it from the
electrical installation. Otherwise the SC300 will again lock the internal teach-in key the
next time the key-operated pushbutton for teach-in is actuated.
Check the effectiveness of the protective device as described in “Test notes” on page 38.