System connection m12 × 8, Connecting the sc300 – Rockwell Automation 442L SC300 Safety Sensor User Manual User Manual
Page 30

28
Rockwell Automation Publication 10000202762 Ver 00 - January 2012
Chapter 5
Electrical installation
•
To meet the requirements of the relevant product standards (e.g. EN 61 4961), the
external voltage supply for the devices (SELV) must be able to bridge a brief mains
failure of 20 ms. Power supplies according to EN 60 2041 satisfy this requirement.
Suitable power supplies are available as accessories from Rockwell Automation (see
“Accessories” section on page 53).
•
Dimension the electrical protection for the camera to suit the information in the
“Data sheet” section on page 47.
System connection M12
× 8
Figure 20 - System connection SC300
The SC300 has a hard-wired connector cable (length: approx. 30 cm) with a cable plug
M12 × 8.
Table 9 - Pin assignment system connection SC300
Note
Connecting cables of different length are available as accessories from Rockwell
Automation (see “Accessories” section on page 53). If you use connecting cables you have
assembled yourself, ensure the functional earth (pin 8) is connected.
Connecting the SC300
Without external device monitoring (EDM), without internal restart interlock
and without external key-operated pushbutton for teach-in
Note
If you use the SC300 without the internal restart interlock, then you must implement the
restart interlock externally, i.e. machine-side.
Pin
Color
Signal
Function
1
White
RESTART
Reset/restart (optional)
2
Brown
+24V DC
24V DC (voltage supply)
3
Green
TEACH/SYNC
Teach-in/synchronization
4
Yellow
EDM
External device monitoring (EDM) (optional)
5
Grey
OSSD1
OSSD1 (safe output signal switching device 1)
6
Pink
OSSD2
OSSD2 (safe output signal switching device 2)
7
Blue
GND
0V DC (voltage supply)
8
–
FE
Functional earth