Events – Rockwell Automation 20-COMM-H RS485 HVAC Adapter FRN 2.xxx User Manual
Page 79

Troubleshooting
8-7
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Events
Many events in the event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help you
or Allen-Bradley personnel troubleshoot the problem. The following events
may appear in the event queue:
Table 8.B Adapter Events
Code Event
Description
1
No Event
Empty event queue entry.
2
DPI Bus Off Flt
A bus-off condition was detected on DPI. This event may be caused by
loose or broken cables or by noise.
3
Ping Time Flt
A ping message was not received on DPI within the specified time.
4
Port ID Flt
The adapter is not connected to a correct port on a DPI product.
5
Port Change Flt
The DPI port changed after start up.
6
Host Sent Reset
The drive sent a reset event message.
7
EEPROM Sum Flt
The EEPROM in the adapter is corrupt.
8
Online @ 125kbps
The adapter detected that the drive is communicating at 125 kbps.
9
Online @ 500kbps
The adapter detected that the drive is communicating at 500 kbps.
10
Bad Host Flt
The adapter was connected to an incompatible product.
11
Dup Port Flt
Another peripheral with the same port number is already in use.
12
Type 0 Login
The adapter has logged in for Type 0 control.
13
Type 0 Time Flt
The adapter has not received a Type 0 status message within the
specified time.
14
DL Login
The adapter has logged into a Datalink.
15
DL Reject Flt
The drive rejected an attempt to log in to a Datalink because the
Datalink is not supported or is used by another peripheral.
16
DL Time Flt
The adapter has not received a Datalink message within the specified
time.
17
Control Disabled
The adapter has sent a “Soft Control Disable” command to the drive.
18
Control Enabled
The adapter has sent a “Soft Control Enable” command to the drive.
19
Message Timeout
A Client-Server message sent by the adapter was not completed within
1 sec.
20
DPI Fault Msg
The drive has faulted.
21
DPI Fault Clear
The drive issued this because a fault was cleared.
22
Normal Startup
The adapter successfully started up.
23
Flt Cfg Error
The adapter detected a 32-bit fault configuration reference when the
drive supports only a 16-bit reference, or detected a 32-bit fault
configuration Datalink value when the drive supports only 16-bit
Datalinks.
24
Net Comm Flt
The adapter detected a communications fault on the network.
25
Net Detected
The adapter has detected network communication.
26
Net TImeout Flt
The adapter has detected a network timeout. The timeout period is
configured in Parameter 11- [Network Timeout].
27
Lang CRC Bad
The CRC of the language text file is incorrect.