Metasys n2 data types – Rockwell Automation 20-COMM-H RS485 HVAC Adapter FRN 2.xxx User Manual
Page 48

5-2
Using Metasys N2
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Metasys N2 Data Types
Table 5.A Description of the Regions of a Virtual Object
Region
Type
Short
Description
Region 1
Analog Input
AI
32-bit, IEEE-standard floats
Region 2
Binary Input
BI
1-bit
Region 3
Analog Output
AO
32-bit, IEEE-standard floats
Region 4
Binary Output
BO
1-bit
Region 5
Internal Float
ADF
32-bit, IEEE-standard floats (Analog Data Float)
Region 6
Internal Integer
ADI
16-bit (Analog Data Integer)
Region 7
Internal Byte
DB
8-bit (Analog Data Byte)
Table 5.B Internal Structure of Metasys N2 Analog Input (AI)
Attribute
Type
Description
1
Byte
Object Configuration
2
Byte
Object Status
3
Float
Analog Input Value
8
Float
Low Alarm Limit
9
Float
Low Warning Limit
10
Float
High Warning Limit
11
Float
High Alarm Limit
12
Float
Differential
Table 5.C Internal Structure of Metasys N2 Binary Input (BI)
Attribute
Type
Description
1
Byte
Object Configuration
2
Byte
Object Status
Table 5.D Internal Structure of Metasys N2 Analog Output (AO)
Attribute
Type
Description
1
Byte
Object Configuration
2
Byte
Object Status
3
Float
Current Value
Table 5.E Internal Structure of Metasys N2 Binary Output (BO)
Attribute
Type
Description
1
Byte
Object Configuration
2
Byte
Object Status
3
Integer
Minimum On-Time
4
Integer
Minimum Off-Time
5
Integer
Maximum Cycle/Hour
Table 5.F Internal Structure of Metasys N2 Internal Integer (ADI)
Attribute
Type
Description
1
Byte
Object Status
2
Integer
Current Value. Signed 16-bit.