Adapter parameter direct access, Adapter parameter direct access -13 – Rockwell Automation 20-COMM-H RS485 HVAC Adapter FRN 2.xxx User Manual
Page 45
Using Modbus RTU
4-13
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Adapter Parameter Direct
Access
Table 4.L
provides an overview of the Modbus register addresses for
directly accessing the adapter parameters.
Table 4.L Adapter Parameter Direct Access Modbus Register Map
Modbus Register
Parameter Description
4x0101
DPI Port
4x0102
DPI Data Rate
4x0103
Net Addr Cfg
4x0104
Net Addr Act
4x0105
Net Rate Cfg
4x0106
Net Rate Act
4x0107
Net Parity Cfg
4x0108
Net Parity Act
4x0109
Stop Bits Act
4x0110
Net Chksum Type
4x0111
Network Timeout
4x0112
Ref/Fdbk Size
4x0113
Datalink Size
4x0114
Reset Module
4x0115
Comm Flt Action
4x0116
DPI I/O Cfg
4x0117
DPI I/O Act
4x0118
Flt Cfg Logic
4x0119
Flt Cfg Ref Lo
4x0120
(1)
(1)
A write access to this register triggers a store/update of this parameter value
to the internal adapter EEPROM as a 32-bit value.
Flt Cfg Ref Hi
4x0121
Flt Cfg A1 In Lo
4x0122
Flt Cfg A1 In Hi
4x0123
Flt Cfg A2 In Lo
4x0124
Flt Cfg A2 In Hi
4x0125
Flt Cfg B1 In Lo
4x0126
Flt Cfg B1 In Hi
4x0127
Flt Cfg B2 In Lo
4x0128
Flt Cfg B2 In Hi
4x0129
Flt Cfg C1 In Lo
4x0130
Flt Cfg C1 In Hi
4x0131
Flt Cfg C2 In Lo
4x0132
Flt Cfg C2 In Hi
4x0133
Flt Cfg D1 In Lo
4x0134
Flt Cfg D1 In Hi
4x0135
Flt Cfg D2 In Lo
4x0136
Flt Cfg D2 In Hi
4x0137
Clear Counters
4x0138
N2 Ref Scale Lo
4x0139
N2 Ref Scale Hi
4x0140
Stop Bits Cfg
4x0141
RTU Ref Adjust