engineering value. For example, in PowerFlex 70/700 drives, the Reference
is scaled based on the value of Parameter 55 - [Maximum Freq], but the
commanded maximum speed can never exceed the value of Parameter 82 -
[Maximum Speed].
Table 6.C
shows example References and their results
on a PowerFlex 70/700 drive that has its Parameters 55 - [Maximum
Freq] set to 130 Hz and 82 - [Maximum Speed] set to 60 Hz.
Table 6.D
shows the commands that you can execute on a PowerFlex 70/
700 drive and the point(s) that you can use to execute them.
Table 6.C Example Speed Reference and Feedback for a PowerFlex 70/700
Reference
Value
Scale
Output Speed
Feedback
Value
Percent
Value
32767
100%
130 Hz
60 Hz
(1)
(1)
The drive runs at 60 Hz instead of 130 Hz because Parameter 82 - [Maximum Speed]
sets 60 Hz as the maximum speed.
15123
(2)
(2)
The Feedback value is also scaled based on the value of Parameter 55 - [Maximum
Freq]. For example, 60/130 = 0.46 so 32767 x 0.46 = 15123.
16384
50%
65 Hz
60 Hz
(1)
15123
8192
25%
32.5 Hz
32.5 Hz
8192
0
0%
0 Hz
0 Hz
0
Table 6.D Logic Commands
Point
Number(s) Point
Logic
Command Bit
PowerFlex 70/700 Example
Descriptio
n
Values
24
CMD RUN.STOP
0
Stop
(1)
0 = Not Stop
1 = Stop
(3)
26
RUN ENABLE
89
LOGIC CMD LO bit 0
24
CMD RUN.STOP
1
Start
(1)
(2)
0 = Not Start
1 = Start
89
LOGIC CMD LO bit 0
89
LOGIC CMD LO bit 2 2
Jog
0 = Not Jog
1 = Jog
94
RESET FAULTS
3
Clear
Faults
(2)
0 = Not Clear Faults
1 = Clear Faults
89
LOGIC CMD LO bit 3
22
CMD FWD.REV
4 and 5
Direction
Bits
89
LOGIC CMD LO
bits 4, 5
05 04
0
0
= No Command
0
1
= Forward Command
1
0
= Reverse Command
1
1
= Hold Direction Control
89
LOGIC CMD LO bit 6 6
Local
Control
0 = No Local Control
1 = Local Control
89
LOGIC CMD LO bit 7 7
MOP
Increment
0 = Not Increment
1 = Increment
90
LOGIC CMD HI
bits 0, 1
8 and 9
Accel Rate
LOGIC CMD HI Bits
01 00
0
0
= No Command
0
1
= Accel Rate 1
1
0
= Accel Rate 2
1
1
= Hold Accel Rate
90
LOGIC CMD HI
bits 3, 2
10 and 11
Decel Rate LOGIC CMD HI Bits
03 02
0
0
= No Command
0
1
= Decel Rate 1
1
0
= Decel Rate 2
1
1
= Hold Decel Rate