6-8
Using Siemens Building Technologies P1 FLN
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
The Feedback can also be viewed in two ways:
•
FREQ OUTPUT (point 03), PCT OUTPUT (point 04), and SPEED
(point 05) report the feedback in values such as Hz, percent of maximum
speed, and RPM, respectively.
•
FEEDBACK (point 91) reports the feedback as a scaled value. For an
explanation of how the Reference/Feedback is scaled, refer to the
the Logic Command and Reference on page 6-5
.
Table 6.E
shows the status that you can view on a PowerFlex 70/700 drive
and the points that you can use to view them.
Table 6.E Logic Status
Point
Number(s) Point Name
Logic
Status Bit
PowerFlex 70/700 Example
Descriptio
n
Values
(1)
25
READY
0
Ready
0 = Not Ready
1 = Ready
95
LOGIC STS LO bit 0
23
RUN.STOP MON
1
Active
0 = Not Running
1 = Running
95
LOGIC STS LO bit 1
95
LOGIC STS LO bit 2 2
Command
Direction
0 = Reverse
1 = Forward
21
FWD.REV MON
3
Actual
Direction
0 = Reverse
1 = Forward
95
LOGIC STS LO bit 3
95
LOGIC STS LO bit 4 4
Accel
0 = Not Accelerating
1 = Accelerating
95
LOGIC STS LO bit 5 5
Decel
0 = Not Decelerating
1 = Decelerating
95
LOGIC STS LO bit 6 6
Alarm
0 = No Alarm
1 = Alarm
93
OK.FAULT
7
Fault
0 = No Fault
1 = Fault
95
LOGIC STS LO bit 7
96
LOGIC STS HI bit 0
8
At Speed
0 = Not At Reference
1 = At Reference
96
LOGIC STS HI
bits 3, 2, 1
9, 10, and 11 Local
Control
LOGIC STS HI Bits
03 02 01
0
0
0
= Port 0 (TB)
0
0
1
= Port 1
0
1
0
= Port 2
0
1
1
= Port 3
1
0
0
= Port 4
1
0
1
= Port 5
1
1
0
= Port 6
1
1
1
= No Local