Using datalinks with siemens p1 fln, Using datalinks with siemens p1 fln -5, Sections – Rockwell Automation 20-COMM-H RS485 HVAC Adapter FRN 2.xxx User Manual
Page 71
Using Datalinks with All Protocols
7-5
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Metasys N2 Datalinks Out: A and B (No Datalinks C and D)
Metasys N2 Datalinks In: A and B (No Datalinks C and D)
Using Datalinks with
Siemens P1 FLN
This section presents information about using Datalinks with Siemens P1
FLN networks. For information about using Datalinks for Modbus networks
or Metasys N2 networks, refer to the
or
Using Datalinks with Metasys N2
sections in this chapter.
DLNK A1 OUT to DLNK D2 OUT contain the Datalink Out A1 to D2
parameters from the drive. DLNK A1 IN to DLNK D2 IN contain the
Datalink In A1 to D2 parameter values to the drive.
For example, a PowerFlex 70 or 700 drive enabling Datalink A for the
adapter and configuring drive Parameter 310 - [Data Out A1] to “1” will
provide drive Parameter 1 - [Output Frequency] at the DLNK A1 OUT
point. Configuring Parameter 300 - [Data In A1] to “140” in the drive will
transfer the value of the DLNK A1 IN point value to drive Parameter 140 -
[Accel Time 1] when accessed.
Table 7.I
Metasys N2 Datalinks Out - A1, A2
Network Point
Type (NPT)
Network Point
Address (NPA) Direction
Parameter
Description
16-Bit
Datalink 32-Bit Datalink
AI
7
Input
Datalink A1 Out 16-bit
value
Limited to
-16,777,215…16,777,215
AI
8
Input
Datalink A2 Out 16-bit
value
Limited to
-16,777,215…16,777,215
Table 7.J Metasys N2 Datalinks Out - B1, B2
Network Point
Type (NPT)
Network Point
Address (NPA) Direction
Parameter
Description
16-Bit
Datalink 32-Bit Datalink
AI
9
Input
Datalink B1 Out 16-bit
value
Limited to
-16,777,215…16,777,215
AI
10
Input
Datalink B2 Out 16-bit
value
Limited to
-16,777,215…16,777,215
Table 7.K Metasys N2 Datalinks In - A1, A2
Network Point
Type (NPT)
Network Point
Address (NPA) Direction
Parameter
Description
16-Bit
Datalink 32-Bit Datalink
AO
5
Output
Datalink A1 In
16-bit
value
Limited to
-16,777,215…16,777,215
AO
6
Output
Datalink A2 In
16-bit
value
Limited to
-16,777,215…16,777,215
Table 7.L Metasys N2 Datalinks In - B1, B2
Network Point
Type (NPT)
Network Point
Address (NPA) Direction
Parameter
Description
16-Bit
Datalink 32-Bit Datalink
AO
7
Output
Datalink B1 In
16-bit
value
Limited to
-16,777,215…16,777,215
AO
8
Output
Datalink B2 In
16-bit
value
Limited to
-16,777,215…16,777,215