beautypg.com

Viewing adapter diagnostic items, Using the him to view adapter diagnostic items, Viewing adapter diagnostic items -4 – Rockwell Automation 20-COMM-H RS485 HVAC Adapter FRN 2.xxx User Manual

Page 76

background image

8-4

Troubleshooting

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

Viewing Adapter Diagnostic
Items

If you encounter unexpected communications problems, the adapter’s
diagnostic items may help you or Rockwell Automation personnel
troubleshoot the problem. Adapter diagnostic items can be viewed using an
LCD PowerFlex 7-Class HIM (Diagnostics/Device Items), DriveExplorer
software (version 2.01 or higher), or DriveExecutive software (version 1.01
or higher).

Using the HIM to View Adapter Diagnostic Items

Step

Keys

Example Screen

1. Access parameters in the adapter. Refer

to

Using the PowerFlex 7-Class HIM on

page 3-2

.

2. Press the Up Arrow or Down Arrow to

scroll to Diagnostics.

3. Press Enter to display the Diagnostics

menu in the adapter.

4. Repeat steps 2 and 3 to enter the Device

Items option.

5. Press the Up Arrow or Down Arrow to

scroll through the items.

Table 8.A Adapter Diagnostic Items

No. Name

Description

1

Common Logic Cmd

The present value of the Common Logic Command being transmitted to
the drive by this adapter.

2

Prod Logic Cmd

The present value of the Product Logic Command being transmitted to
the drive by this adapter.

3

Reference

The present value of the Reference being transmitted to the drive by this
adapter. Note that a 16-bit value will be sent as the Most Significant
Word of the 32-bit field.

4

Common Logic Sts

The present value of the Common Logic Status being received from the
drive by this adapter.

5

Prod Logic Sts

The present value of the Product Logic Status being received from the
drive by this adapter.

6

Feedback

The present value of the Feedback being received from the drive by this
adapter. Note that a 16-bit value will be sent as the Most Significant
Word of the 32-bit field.

7

Datalink A1 In

The present value of respective Datalink In being transmitted to the
drive by this adapter. (If not using a Datalink, this parameter should have
a value of zero. Refer to

Chapter 7

,

Using Datalinks with All Protocols

for

information about Datalinks.)

8

Datalink A2 In

9

Datalink B1 In

10

Datalink B2 In

11

Datalink C1 In

12

Datalink C2 In

13

Datalink D1 In

14

Datalink D2 In

or

or

Main Menu:

Diagnostics

Parameter
Device Select

Device Item #

27

Net Packet Rcvd

1022