Using Modbus RTU

20-COMM-H RS-485 HVAC Adapter User Manual

Publication 20COMM-UM009D-EN-P

Figure 4.1

Configurable Input Point Operations

With the adapter in 16-bit mode, 8 User IN items are available.

16-bit Mode Example: Write a value of “12” to register 4x0004. Read
register 3x0004 to read the 16-bit data value from drive parameter 12.

With the adapter in 32-bit mode, 4 User IN items are available.

32-bit Mode Example: Write a value of “12” to register 4x0004. Read
register 3x0004 and store the returned 16-bit data. Read register 3x0005 and

Table 4.I

Configurable Objects Inputs with Adapter in 16-bit Mode

Modbus
Address

Data Direction

Description

Values

User
Default

3x0004

Register Input

User IN1

Depends on parameter selected

0

3x0005

User IN2

3x0006

User IN3

3x0007

User IN4

3x0008

User IN5

3x0009

User IN6

3x0010

User IN7

3x0011

User IN8

4x0004

Register Output

Param # for IN1

0 = Not in use
- or -
1 to maximum parameter #

0

4x0005

Param # for IN2

4x0006

Param # for IN3

4x0007

Param # for IN4

4x0008

Param # for IN5

4x0009

Param # for IN6

4x0010

Param # for IN7

4x0011

Param # for IN8

Table 4.J Configurable Objects Inputs with Adapter in 16-bit Mode

Modbus
Address

Data Direction

Description

Values

User
Default

3x0004
3x0005

Register Input

User IN1 Lo
User IN1 Hi

Depends on parameter selected

0

3x0006
3x0007

User IN2 Lo
User IN2 Hi

3x0008
3x0009

User IN3 Lo
User IN3 Hi

3x0010
3x0011

User IN4 Lo
User IN4 Hi

4x0004

Register Output

Param # for IN1

0 = Not in use
- or -
1 to maximum parameter #

0

4x0005

Param # for IN2

4x0006

Param # for IN3

4x0007

Param # for IN4

Controller

Adapter

and

Drive

Param#

for INx

User

INx

Write Single Register (code 06)

or

Write Multiple Register (code 16)

Read Input Registers (code 04) Request

Response Data