Control and signal wiring – Rockwell Automation 23C PowerFlex 400 AC Drive Packages for Fan & Pump Apps User Manual
Page 92
![background image](/manuals/577252/92/background.png)
92
Rockwell Automation Publication 23C-IN001B-EN-P - June 2013
Chapter 2
3 Contactor Full Feature Bypass with Disconnect Package (Style B/N)
Control and Signal Wiring
Refer to the PowerFlex 400 User Manual for additional detailed information
about control and signal wiring.
The Signal Terminal Block (TB1 Terminals 1…20 and R1…R6) located on the
drive Main Control Board and Control Terminal Block (TB1 Terminals 31…40)
located inside the Option Cabinet provide terminals for interfacing customer
supplied control inputs and outputs. All analog and discrete control wiring will
be made at these terminals. Typical customer control and signal wiring is shown
on the Interconnect drawings,
on page
and
on page
.
To connect control and signal wiring to the drive package:
❏
1. Wire the control and signal leads by routing them according to the drive
option type. Note that you must punch openings in the option cabinet of
the desired conduit size, following NEC and all applicable local codes and
standards. Control and signal terminal block specifications are listed in
.
Control and signal wires should be separated from power wires by at least
0.3 meters (1 foot).
❏
2. Connect the analog and relay output signal wiring to terminals 1…20 and
R1…R6 located on the drive Main Control Board.
❏
3. Connect the control wiring listed below to terminals 31…40 located inside
the Option Cabinet.
– Interlock
– Freeze/Fire Stats
– Autostart
– Bypass
– Purge
– Bypass Running
❏
4. Tighten the control and signal terminals to the proper torque according to
Table 9 - Control and Signal Terminal Block Specifications
Voltage Rating Terminals
Location
Maximum Wire
Size
(1)
(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
Minimum Wire Size Torque
208…460V AC
1…20,
R1…R6
Main Control
Board
1.3 mm
2
(16 AWG)
0.13 mm
2
(26 AWG)
0.5-0.8 N•m (4.4-7
lb•in)
31…40
Option Cabinet 4.0 mm
2
(10 AWG)
0.5 mm
2
(22 AWG)
0.6 N•m
(5.0 lb•in)