Electrical installation, Input power wiring – Rockwell Automation 23C PowerFlex 400 AC Drive Packages for Fan & Pump Apps User Manual
Page 90
90
Rockwell Automation Publication 23C-IN001B-EN-P - June 2013
Chapter 2
3 Contactor Full Feature Bypass with Disconnect Package (Style B/N)
Electrical Installation
Input Power Wiring
Use 75 °C rated copper conductors only for customer power wiring.
Refer to the PowerFlex 400 User Manual for additional detailed information
about input power wiring recommendations and selection.
To connect AC input power to the drive package:
❏
1. Select the proper wire size according to NEC and all applicable local codes
and standards. Note that you must punch openings in the Option Cabinet
of the desired conduit size, following NEC and all applicable local codes
and standards. Power terminal block specifications are listed in
❏
2. Connect the three-phase AC input power leads (three-wire VAC) to the
appropriate terminals. Connect the AC input power leads to terminals
L1, L2, L3 on the fused disconnect switch.
❏
3. Tighten the AC input terminal power terminals to the proper torque
according to drive type as shown in
.
Table 7 - AC Input Power Terminal Block Specification
ATTENTION: Protect the contents of the options cabinet from metal chips and
other debris while drilling the conduit openings. Failure to observe this
precaution could result in damage to, or destruction of, the equipment.
ATTENTION: Do not route signal and control wiring with power wiring in the
same conduit. This can cause interference with drive operation. Failure to observe
this precaution could result in damage to, or destruction of, the equipment.
Volts
AC
kW
Hp
Maximum Wire Size
(1)
(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations. If national or local codes require
sizes outside the range, lugs may be used.
Minimum Wire Size
Recommended Torque
208V
2.2…3.7
3.0…5.0
8.4 mm
2
(8 AWG)
2.5 mm
2
(14 AWG)
4.0 N•m (35 lb•in)
5.5…7.5
7.5…10
16.0 mm
2
(4 AWG)
2.5 mm
2
(14 AWG)
4.0 N•m (35 lb•in)
11…15
15…20
33.6 mm
2
(2 AWG)
2.5 mm
2
(14 AWG)
17.5 N•m (155 lb•in)
18.5…30 25…40
250 MCM
10.0 mm
2
(6 AWG)
31.1 N•m (275 lb•in)
37
50
350 MCM
35.0 mm
2
(1/0 AWG)
31.1 N•m (275 lb•in)
460V
2.2…7.5
3.0…10
8.4 mm
2
(8 AWG)
2.5 mm
2
(14 AWG)
4.0 N•m (35 lb•in)
11…18.5 15…25
16.0 mm
2
(4 AWG)
2.5 mm
2
(14 AWG)
4.0 N•m (35 lb•in)
22…37
30…50
33.6 mm
2
(2 AWG)
2.5 mm
2
(14 AWG)
17.5 N•m (155 lb•in)
45…75
60…100
250 MCM
10.0 mm
2
(6 AWG)
31.1 N•m (275 lb•in)
90…110
125…150 (2) 350 MCM
(2) 10.0 mm
2
(6 AWG)
31.1 N•m (275 lb•in)
132
200
(2) 350 MCM
(2) 35.0 mm
2
(1/0 AWG)
31.1 N•m (275 lb•in)
160…200 250…300 (2) 350 MCM
(2) 70.0 mm
2
(3/0 AWG)
31.1 N•m (275 lb•in)
250
350
(2) 400 MCM
(2) 70.0 mm
2
(3/0 AWG)
31.1 N•m (275 lb•in)