This chapter provides information on electrical installation of a PowerFlex Drive
Package for Fan and Pump Applications.
Power Wire Size
Requirements
Wire size should be determined based on the size of the conduit openings, and
applicable local, national and international codes such as NEC/CEC.
Power Terminal Block
Specification
Input power wiring should be sized according to applicable codes to handle the
drive's continuous-rated input current. Output wiring should be sized according
to applicable codes to the handle the drive's continuous-rated output current. See
for the range of power wire sizes that the terminals can accommodate.
Table 14 - Power Wire Sizes
Topic
Page
Power Terminal Block Specification
Installing Output Power Wiring
Installing an Optional Transformer or Reactor
ATTENTION: National codes and standards (NEC, VDE, BSI, etc.) and local codes
outline provisions for safely installing electrical equipment. Installation must
comply with specifications regarding wire types, conductor sizes, branch circuit
protection, and disconnect devices. Failure to do so may result in personal injury
and/or equipment damage.
Name
Package
Style
Hp
Wire Size Range
Torque
208V AC
480V AC
Minimum
Maximum
Input Power
L1(R), L2 (S), L3 (T)
A & B
3…5
3…10
14 AWG
8 AWG
12
7.5…10
15…25
14 AWG
4 AWG
35
15…20
30…50
14 AWG
2 AWG
35
25…40
60…100
6 AWG
250 MCM
275
50
125…200
(2) 1/0
350 MCM
275
–
250…300
(2) 2/0
350 MCM
275
–
350
(3) 3/0
350 MCM
275