Catalog number explanation – Rockwell Automation 23C PowerFlex 400 AC Drive Packages for Fan & Pump Apps User Manual
Page 10

10
Rockwell Automation Publication 23C-IN001B-EN-P - June 2013
Preface
Catalog Number Explanation
The PowerFlex 400 Adjustable Frequency AC Drive Packages for Fan & Pump
Applications catalog numbering scheme is shown below.
Position
1-3
4
5
6-8
9
10
11
12
13
14
15
16
17
18
19+
23C
–
D
038
A
1
0
3
N
N
B
A
N
N
-LR
a
b
c
d
e
f
g
h
i
j
k
l
m
n
a
Drive
Code
Type
23C
PowerFlex 400
b
Voltage Rating
Code
Voltage
Ph.
X
208V ac
3
D
480V ac
3
c1
Rating
208V, 60Hz Input
Code
Amps
kW (Hp)
Frame
012
12
2.2 (3.0)
C
017
16.8
3.7 (5.0)
C
024
24
5.5 (7.5)
C
033
30.8
7.5 (10)
C
049
46.2
11 (15)
D
065
64
15 (20)
D
075
75
18.5 (25)
D
090
88
22 (30)
D
120
114
30 (40)
E
145
143
37 (50)
E
Configured drive amp ratings may differ from
stand-alone drive ratings. Configured drives
sized per NEC motor amps.
d
Enclosure
Code
Enclosure
A
NEMA/UL Type 1
H
NEMA/UL Type 12 with Fan and
Filter
X
NEMA/UL Type 3R ‡
E
NEMA/UL Type 4 ‡
‡ Designed for maximum ambient temperature of
40° C with no direct sunlight exposure.
e
HIM
Code
Interface Module
1
Fixed Keypad
f
Emission Class
Code
Rating
0
Not Filtered
j
Package
Code
Description
A
Main Input Disconnect
B
3 Contactor Full Feature Bypass
with Disconnect
M
Main Input Circuit Breaker
N
3 Contactor Full Feature Bypass
with Circuit Breaker
Available with all ratings in NEMA/UL Type 12,
3R, or 4 enclosures (Position d = H, X, or E)
and 160-250 kW (250-350 Hp) ratings in
NEMA/UL Type 1 enclosures (Position d = A).
k
Control
Code
Description
A
Single Motor
l
Code
Rating
N
Reserved
c2
Rating
460V, 60Hz Input
Code
Amps
kW (Hp)
Frame
6P0
4.8
2.2 (3.0)
C
010
7.6
4.0 (5.0)
C
012
11
5.5 (7.5)
C
017
14
7.5 (10)
C
022
21
11 (15)
C
030
27
15 (20)
C
038
34
18.5 (25)
D
045
40
22 (30)
D
060
52
30 (40)
D
072
65
37 (50)
E
088
77
45 (60)
E
105
96
55 (75)
E
142
124
75 (100)
E
170
156
90 (125)
F
208
180
110 (150)
F
260
240
132 (200)
G
310
302
160 (250)
G
370
361
200 (300)
H
460
414
250 (350)
H
Configured amp ratings may differ from stand-
alone drive ratings. Configured drives sized per
NEC motor amps.
g
Version
Code
Version
3
RS485
B
BACnet Adapter
C
ControlNet Adapter
D
DeviceNet Adapter
E
EtherNet/IP Adapter
L
LonWorks Adapter
P
PROFIBUS DP Adapter
h
Code
Rating
N
Reserved
i
Code
Rating
N
Reserved
m
Code
Rating
N
Reserved
n
Options
Code
Description
-LR
3% Input Line Reactor §
-E5
Space Heater - Local Power
♣
§ 3% Input Line Reactor not available for all
package styles. Consult product selection
tables for additional detail.
♣
Available with NEMA/UL Type 3R and 4
enclosures only.
‡ Not available with all ratings at 460V. Consult
product selection tables for details.
‡
Not available with all ratings at 460V. Consult
product selection tables for details.