Drivelogix controller leds – Rockwell Automation 5720 DriveLogix System User Manual
Page 244
Publication 20D-UM002C-EN-P - November 2003
A-6 DriveLogix System Specifications
DriveLogix Controller LEDs
Type
Name
Color
State
Description
Daughtercard
LEDs
PORT
Green
–
Status of DPI port internal communications (if
present).
MOD
Yellow –
Status of communications module (when installed).
NET A
Red
–
Status of network (if connected).
NET B
Red
–
Status of secondary network (if connected).
NET A
OFF
No power,
Host is faulted,
Host is holding daughtercard in reset.
Red
Steady
Major Fault
Red
Flashing
Minor Fault
Green
Flashing
No connections established
Green
Steady
Connections established
NET B
OFF
No power,
Host is faulted,
Host is holding daughtercard in reset.
Red
Steady
Major Fault
Red
Flashing
Minor Fault
Green
Flashing
No connections established
Green
Steady
Connections established
Controller
LEDs
RUN
Green
Off
No task(s) running.
Controller in Program mode.
Green
Steady
One or more tasks are running.
Controller is in Run mode.
FORCE
Amber Off
No forces present.
Amber Steady
Forces present and enabled.
Amber Flashing
Forces present but not enabled.
BATT
Red
Off
Battery will support memory.
Red
Steady
Battery may not support memory - replace battery.
I/O
Green
Off
Controller project not downloaded (the condition
after power up).
No I/O or communications configured.
Green
Steady
Communicating to all devices.
Green
Flashing
One or more devices are not responding.
Red
Flashing
No required I/O connections can be made, controller
is in Run mode.
RS 232
Green
Off
No activity.
Green
Flashing
Data being received or transmitted.
OK
Off
No power applied.
Red
Flashing
Recoverable fault or flash programming.
Red
Steady
Controller faulted.
Clear faults, clear memory, or replace the controller.
Green
Steady
Controller OK.