Placing and Configuring Local I/O 4-17
• inputs remain in their last, non-faulted state
Configure critical I/O modules to generate a controller major fault when they
lose their connections to the controller. Or, monitor the status of I/O
modules.
Monitoring an I/O module
Most I/O modules have fault bits that indicate when a fault occurs at a specific
point of a module. To view this data through the programming software:
You can write logic to monitor these bits and take appropriate action if a fault
occurs. For example, you may want to shut down the system if a specific point
ATTENTION
!
If a module loses its connection to the controller, the
controller and other I/O modules continue to operate
based on old data from that module. To avoid potential
personal injury and damage to machinery, make sure this
does not create unsafe operation.
1. In the Controller Organizer, select Controller Tags. Right-click to select Monitor Tags.