6-30 Communicating with Devices on an EtherNet/IP Link

The PLC-5 controller supports logical ASCII addressing so you do not have to
map a compatibility file for MSG instructions initiated by a PLC-5 controller.
Place the DriveLogix tag name in double quotes (“).

Example 3: Total connections required by DriveLogix1

The following table calculates the connections used in this example.

If you configured the local I/O modules as rack-optimized, you would only
need the DIN-rail connection to the I/O modules, reducing the above
example by 3 connections.

Typed Write

SINT or INT tag

any integer element (such as B3:0,
T4:0.ACC, C5:0.ACC, N7:0, etc.)

REAL tag

any floating point element (such as F8:0,
PD10:0.SP, etc.)

Word Range Read

any data type (such as B3:0, T4:0, C5:0,
R6:0, N7:0, F8:0, etc.)

SINT, INT, DINT, or REAL

Word Range Write

SINT, INT, DINT, or REAL

any data type (such as B3:0, T4:0, C5:0,
R6:0, N7:0, F8:0, etc.)

Type of Logix MSG instruction:

Source:

Destination:

Type of MSG Instruction:

Example Source and Destination:

PLC-5 writes to DriveLogix

source element

N7:10

destination tag

“array_1”

PLC-5 reads from DriveLogix

source tag

“array_1”

destination element

N7:10

Connection:

Amount:

DriveLogix1 controller to 3 local I/O modules

rack-optimized connection for the DIN rail

direct connection for each I/O module

1

3

DriveLogix1 controller to local 1788-ENBT

0

connected, cached MSG from DriveLogix1 to Control1

1

connected, cached MSG from DriveLogix1 to PLC-5E1

1

total connections used: 6