beautypg.com

Rockwell Automation 5720 DriveLogix System User Manual

Page 218

background image

Publication 20D-UM002C-EN-P - November 2003

10-8 Communicating with Devices on a DH-485 Link

Connections Using Belden 9842 Cable

The table and schematic diagram below shows wire/terminal connections for
Belden 9842 cable.

For this Wire/Pair

Connect this Wire

To this Terminal

white/orange

orange with white stripe

5 - (Data A)

white with orange stripe

4 - (Data B)

blue/white

white with blue stripe

cut back - no connection

(1)

(1)

To prevent confusion when installing the communication cable, cut back the white with blue stripe wire
immediately after the insulation jacket is removed. This wire is not used by DH-485.

blue with white stripe

3 - (Common)

shield/drain

non-jacketed

2 - Shield

Termination

Data A

Data B

Common

Shield

Chassis Ground

WH/OR

OR/WH

6

5

4

3

2

1

WH/BU

BU/WH

This manual is related to the following products: