Rockwell Automation 20-COMM-I Interbus Adapter User Manual
Page 97

Adapter Parameters
B-3
09
[DPI I/O Active]
I/O that the adapter is actively transmitting. The
value of this parameter will usually be equal to the
value of Parameter 8 - DPI I/O Config.
Default:
xxx0 0001
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read Only
Bit Definitions
0 = Cmd/Ref
1 = Datalink A
2 = Datalink B
3 = Datalink C
4 = Datalink D
5 = Not Used
6 = Not Used
7 = Not Used
10
[Flt Cfg Logic]
Sets the Logic Command data that is sent to the
drive if any of the following is true:
• Parameter 06 - [Comm Flt Action] is set to
Send Flt Cfg and communications are
disrupted.
The bit definitions will depend on the product to
which the adapter is connected.
Default:
0000 0000 0000 0000
Minimum:
0000 0000 0000 0000
Maximum:
1111 1111 1111 1111
Type:
Read/Write
Reset Required:
No
11
[Flt Cfg Ref]
Sets the Reference data that is sent to the drive if
any of the following is true:
• Parameter 06 - [Comm Flt Action] is set to
Send Flt Cfg and communications are
disrupted.
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read/Write
Reset Required:
No
Important: If the drive uses a 16-bit
Reference, the most significant word of this
value must be set to zero (0) or a fault will
occur.
12
13
14
15
16
17
18
19
[Flt Cfg A1]
[Flt Cfg A2]
[Flt Cfg B1]
[Flt Cfg B2]
[Flt Cfg C1]
[Flt Cfg C2]
[Flt Cfg D1]
[Flt Cfg D2]
Sets the data that is sent to the Datalink in the
drive if any of the following is true:
• Parameter 06 - [Comm Flt Action] is set to
Send Flt Cfg and the communications are
disrupted.
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read/Write
Reset Required:
No
Important: If the drive uses 16-bit
Datalinks, the most significant word of this
value must be set to zero (0) or a fault will
occur.
20
PIDD W0 Cfg
Configured Process Input Data Description for
Word 0. PCP Object to use for Word 0 transmitted
to Interbus master.
Default:
0x2F9A
(Logic Status)
Setting:
Type:
Read/Write
Reset Required:
No (becomes active
when Interbus network
is restarted)
21
PIDD W0 Actual
Actual Process Input Data Description for Word 0.
Value:
Type:
Read Only
Parameter
No. Name and Description
Details
Bit
Default
1
0
0
0
0
x x
x
0
1
2
3
4
5
7
6
20COMM-UM007A-EN-P.book Page 3 Tuesday, January 22, 2002 10:52 AM