Cable check (cc) status indicator, Remote bus disable (rd) status indicator, Transmit/receive (tr) status indicator – Rockwell Automation 20-COMM-I Interbus Adapter User Manual
Page 86: Remote bus disable (rd) status indicator -2
7-2
Troubleshooting
Note: The UL indicator is not viewable when the drive cover is installed
or closed.
Note: Interbus compliance requires different LED functions than what is
normally displayed on the front of the drive (Port, Mod, Net A and Net B
Leds). LED labels are provided with the adapter for application to the
drive cover.
Cable Check (CC) Status Indicator
Status
Cause
Corrective Action
Off
Master is reset or no cable
connection.
• Connect the adapter to the network using an
Interbus cable.
• Verify master not in reset.
Solid Green
Cable connection good.
• No Action.
Remote Bus Disable (RD) Status Indicator
Status
Cause
Corrective Action
Off
Outgoing remote bus is not
switched off.
• No action.
Solid Red
Outgoing remote bus is
switched off.
• Read configuration or start data
transmission. Master may have to be reset
first.
Transmit/Receive (TR) Status Indicator
Status
Cause
Corrective Actions
Off
No PCP connection is
carried out.
• Verify that master is sending PCP
messages.
Solid Green
A PCP connection is being
carried out. Flashes when
a new PCP frame has
been received.
• No action.