beautypg.com

Cable check (cc) status indicator, Remote bus disable (rd) status indicator, Transmit/receive (tr) status indicator – Rockwell Automation 20-COMM-I Interbus Adapter User Manual

Page 86: Remote bus disable (rd) status indicator -2

background image

7-2

Troubleshooting

Note: The UL indicator is not viewable when the drive cover is installed
or closed.

Note: Interbus compliance requires different LED functions than what is
normally displayed on the front of the drive (Port, Mod, Net A and Net B
Leds). LED labels are provided with the adapter for application to the
drive cover.

Cable Check (CC) Status Indicator

Status

Cause

Corrective Action

Off

Master is reset or no cable
connection.

• Connect the adapter to the network using an

Interbus cable.

• Verify master not in reset.

Solid Green

Cable connection good.

• No Action.

Remote Bus Disable (RD) Status Indicator

Status

Cause

Corrective Action

Off

Outgoing remote bus is not
switched off.

• No action.

Solid Red

Outgoing remote bus is
switched off.

• Read configuration or start data

transmission. Master may have to be reset
first.

Transmit/Receive (TR) Status Indicator

Status

Cause

Corrective Actions

Off

No PCP connection is
carried out.

• Verify that master is sending PCP

messages.

Solid Green

A PCP connection is being
carried out. Flashes when
a new PCP frame has
been received.

• No action.

20COMM-UM007A-EN-P.book Page 2 Tuesday, January 22, 2002 10:52 AM