3-4
Configuring the Adapter
4. Interbus requires the network I/O mapping to be configured first in
the adapter. CMD software will read this configuration online when
it is configuring the scanner.
Process Input Data Description (PIDD) words map input data on the
network (data seen as inputs to the scanner and controller program).
Example input data includes Logic Status, Feedback and Datalinks
(Datalink x1 Out). Up to 9 words of input data can be mapped.
Process Output Data Description (PODD) words map output data on
the network (data sent as outputs from the scanner and controller
program). Example output data includes Logic Command, Reference
and Datalinks (Datalink x1 In). Up to 9 words of output data can be
mapped.
The following indexes are used to select the I/O data:
Table 3.1 PIDD/PODD Indexes
Value
(Hex)
Value
(Dec)
Selects
2F9A
12186
Logic Status
2F9B
12187
Feedback
2FA4
12196
Datalink A1 Out
2FA5
12197
Datalink A2 Out
2FA6
12198
Datalink B1 Out
2FA7
12199
Datalink B2 Out
2FA8
12200
Datalink C1 Out
2FA9
12201
Datalink C2 Out
2FAA
12202
Datalink D1 Out
2FAB
12203
Datalink D2 Out
Value
(Hex)
Value
(Dec)
Selects
2F98
12184
Logic Command
2F99
12185
Reference
2F9C
12188
Datalink A1 In
2F9D
12189
Datalink A2 In
2F9E
12190
Datalink B1 In
2F9F
12191
Datalink B2 In
2FA0
12192
Datalink C1 In
2FA1
12193
Datalink C2 In
2FA2
12194
Datalink D1 In
2FA3
12195
Datalink D2 In
Input
Output