Rockwell Automation 20-COMM-I Interbus Adapter User Manual
Page 27

Configuring the Adapter
3-5
To configure the adapter for Logic Command/Status, Reference/
Feedback and the maximum number of Datalinks enabled:
Note that Datalink D2 is not used in this example because maximum
configuration has been reached. The maximum configuration is shown to
illustrate utilizing all 9 words of inputs and 9 words of outputs.
Depending on your application needs, any subset of the above example
can be implemented.
The corresponding Parameter 8 - [DPI I/O Config] setting would be
“11111” for all of the above information to transfer between the adapter
and the drive.
5. Reset the adapter. Refer to the
section in this
chapter.
The adapter is ready to receive I/O from the master (i.e., scanner). You
must now configure the scanner to recognize and transmit I/O to the
adapter. Refer to
Configuring the Interbus Scanner
Parameter #
Name
Value
(Hex)
Value
(Dec)
Description
20
PIDD W0 Cfg
2F9A
12186
Logic Status (default)
22
PIDD W1 Cfg
2F9B
12187
Feedback (default)
24
PIDD W2 Cfg
2FA4
12196
Datalink A1 Out
26
PIDD W3 Cfg
2FA5
12197
Datalink A2 Out
Input
28
PIDD W4 Cfg
2FA6
12198
Datalink B1 Out
30
PIDD W5 Cfg
2FA7
12199
Datalink B2 Out
32
PIDD W6 Cfg
2FA8
12200
Datalink C1 Out
34
PIDD W7 Cfg
2FA9
12201
Datalink C2 Out
36
PIDD W8 Cfg
2FAA
12202
Datalink D1 Out
38
PODD W0 Cfg
2F98
12184
Logic Command (default)
40
PODD W1 Cfg
2F99
12185
Reference (default)
42
PODD W2 Cfg
2F9C
12188
Datalink A1 In
44
PODD W3 Cfg
2F9D
12189
Datalink A2 In
Output
46
PODD W4 Cfg
2F9E
12190
Datalink B1 In
48
PODD W5 Cfg
2F9F
12191
Datalink B2 In
50
PODD W6 Cfg
2FA0
12192
Datalink C1 In
52
PODD W7 Cfg
2FA1
12193
Datalink C2 In
54
PODD W8 Cfg
2FA2
12194
Datalink D1 In
20COMM-UM007A-EN-P.book Page 5 Tuesday, January 22, 2002 10:52 AM