Configuring the Interbus Scanner
4-15
PowerFlex 70 Settings to use with Ladder Examples
The following parameters should be configured to use the example
ladder logic program.
PowerFlex 70
RSLogix 500 SST Interbus Scanner Configuration
The SST Interbus scanner is configured by clicking on the I/O
Configuration in RSLogix500. The SST-IBS-SLC has an ID Code of
13635. The following settings are used by the example ladder logic
program, as shown in
and
.
Parameter Name
Value
Description
90
Speed Ref A Sel
22
DPI Port 5 (20-COMM-I) provides the
Reference
300
Data In A1
140
Pr. 140 [Accel Time 1]
301
Data In A2
142
Pr. 142 [Decel Time 1]
302
Data In B1
100
Pr. 100 [Jog Speed]
303
Data In B2
155
Pr. 155 [Stop Mode A]
304
Data In C1
101
Pr. 101 [Preset Speed 1]
305
Data In C2
102
Pr. 102 [Preset Speed 2]
306
Data In D1
103
Pr. 103 [Preset Speed 3]
310
Data Out A1
140
Pr. 140 [Accel Time 1]
311
Data Out A2
142
Pr. 142 [Decel Time]
312
Data Out B1
100
Pr. 100 [Jog Speed]
313
Data Out B2
155
Pr. 155 [Stop Mode A]
314
Data Out C1
101
Pr. 101 [Preset Speed 1]
315
Data Out C2
102
Pr. 102 [Preset Speed 2]
316
Data Out D1
103
Pr. 103 [Preset Speed 3]