B-2
Serial Converter Module Parameters
No.
Name and Description
Details
05
[Reset Module]
No action if set to “Ready.” Resets the serial converter
module if set to “Reset Module.” Restores the module
to its factory-default settings if set to “Set Defaults.”
This parameter is a command. It will be reset to “0 =
Ready” after the command has been performed.
Default:
0 = Ready
Values:
0 = Ready
1 = Reset Module
2 = Set Defaults
Type:
Read/Write
06
[Clear DF1 Counts]
No action if set to “Ready.” Resets the DF1 statistical
parameters (numbers 07 – 15) to 0 if set to “Clear
Counts.” This parameter is a command. It will be reset
to “0 = Ready” after the command has been
performed.
Default:
0 = Ready
Values:
0 = Ready
1 = Clear Counts
Type:
Read/Write
Reset Required: No
07
[DF1 Packets Sent]
Displays the number of DF1 packets sent by the serial
converter module. The value of this parameter is
normally approximately equal to the value of
Parameter 08 - [DF1 Packets Rcvd].
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read Only
08
[DF1 Packets Rcvd]
Displays the number of DF1 packets received by the
serial converter module. The value of this parameter is
normally approximately equal to the value of
Parameter 07 - [DF1 Packets Sent].
Default:
0
Minimum:
0
Maximum:
4294967295
Type:
Read Only
09
[Undelivered Msgs]
(1)
Displays the number of DF1 messages that were sent
but not acknowledged.
Default:
0
Minimum:
0
Maximum:
65535
Type:
Read Only
10
[ENQs Sent]
(1)
Displays the number of ENQ characters sent by the
serial converter module.
Default:
0
Minimum:
0
Maximum:
65535
Type:
Read Only
11
[ENQs Received]
(1)
Displays the number of ENQ characters received by
the serial converter module.
Default:
0
Minimum:
0
Maximum:
65535
Type:
Read Only
12
[NAKs Received]
(1)
Displays the number of NAK characters received by
the serial converter module.
Default:
0
Minimum:
0
Maximum:
65535
Type:
Read Only
13
[NAK Bad Packet]
(1)
Displays the number of NAKs sent by the serial
converter module because of corrupt packets
(improper protocol messages) as determined by the
module.
Default:
0
Minimum:
0
Maximum:
65535
Type:
Read Only
(1)
This value is normally a low value. If it is continually incrementing and you are having
communications problems, use a lower baud rate or replace the 1203-SFC serial cable.
!
ATTENTION: Risk of injury or equipment damage exists. If the serial
converter module is transmitting I/O that controls the drive (indicated by a
solid green diamond LED), the drive may fault when you remove or reset the
module. Determine how your drive will respond before removing or resetting
a connected serial converter module.