Events – Rockwell Automation 22-SCM-232 Serial Converter Module User Manual
Page 36
![background image](/manuals/576865/36/background.png)
5-4
Troubleshooting
Events
Many events in the Event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help
you or Allen-Bradley personnel troubleshoot the problem. The following
events may appear in the event queue:
To clear the event queue
1. Access the event queue using a configuration tool. Refer to the
Configuration Tools
section in
Chapter 3
.
2. Set the value of 1 > Clr Event Queue to Enable, and then press
Enter to clear the event queue.
Figure 5.3 Reset Event Queue in HyperTerminal
Code
Event
Description
F0
No Event
No event present in the module event queue.
F1
Adapter Reset
The module was reset by the user.
F2
Slave Detected
Slave was detected to be present by master.
F3
Slave Removed
Slave was detected to be removed by master.
F4
Host Timeout
Timeout condition on Msg to Host.
F5
Slave Timeout
Timeout condition on Msg to Slave.
F6
Master Timeout
Timeout condition on Msg to Master.
F7
Serial Timeout
Timeout on Serial 232 side (w/control enabled).
F8
Control Enabled
The module has sent a “Soft Control Enable” command
to the drive.
F9
Control Disabled
The module has sent a “Soft Control Disable”
command to the drive.
F10
EEPROM Sum Flt
Startup sequence detected corrupt EEPROM storage
in the module.
Press the UP ARROW or DOWN ARROW key to scroll
through the parameter list. Press the LEFT ARROW or
RIGHT ARROW key to modify parameter values. Press
the ENTER key to save a new value.
1> Clr Event Queue = Enable