Ulticast, Anager, Multicast pipe manager – Weidmuller WI-MOD-945-E: 900Mhz Wireless Ethernet & Device Server v2.16 User Manual
Page 46: 12 - multicast pipe manager
Weidmuller Wireless Ethernet Modem & Device Server WI-MOD-945-E User Manual
Page 46
www.weidmuller.com
Rev 2.136
3.12 - Multicast Pipe Manager
Previously it has been difficult to connect a single TCP device, i.e. a
Scada / DCS system to multiple remote multicast serial devices.
Multicast Pipe allows this type of connection.
Example:
An example would be a Scada system that needs to communicate
with multiple remote serial devices. A modem can be placed at each
remote location and connected serially to each device. A multicast
pipe is configured to communicate with all devices using a multicast
address and port, i.e. 224.0.1.1:5000.
The Scada then communicates with the remotes using TCP via the
IP address of the Multicast Manager and the port selected in the
configuration, i.e. 5001.
Multicast Pipe Manager
Enabled
Enables or disables the Multicast Pipe manager.
Server Port
Server port used by the Multicast Pipe Manager. Will need to be
configured the same as the Port on the Client, i.e. Scada, DCS, etc
Multicast Group IP
Address
Broadcast Address used when communicating to all other Multicast
devices. This address will need to be the same on all communicating
Multicast devices.
Multicast Group Port
Multicast Port used when communicating to all other Multicast devices.
Will need to be the same on all communicating Multicast devices.
Figure 25 - Multicast Pipe
Figure 26 - Multicast Group