3.11 - Serial Menu
RS-232 / RS485 Serial Port Configuration (Common to all)
RS232 Port
Select the desired functionality. Select either PPP, Serial Gateway or Modbus TCP
to RTU
Data Rate
The serial data rate desired. Serial data rates available range from 110bps to a
maximum of 115,200bps.
Data Format
The data format desired. All the standard data formats are supported.
Flow Control
Selects CTS/RTS or None
RS232 PPP Server (Only RS232)
Username
User name to enter to access RS-232 PPP Server.
Password
Password to access RS-232 PPP Server.
Local IP
Address
Select the IP address of the PPP server. The remote device may be made visible
on the Ethernet or Wireless networks by either utilising proxy-arp or routing. The
proxy-arp feature may be enabled by setting the Local IP address the same as the
Ethernet IP Address or the Wireless IP Address. The module will respond on behalf
of the remote device, making it seem like the device is present on the configured
network. Alternatively, if the IP address selected is not the same as the Ethernet or
Wireless IP address, routing is used to pass data to the Ethernet and Wireless
ports.
Remote
Device IP
Address
Select the IP address of the remote device. Ensure this address is not the same as
any other device on the Ethernet or Wireless networks.
RS-232 / RS485 Serial Gateway Mode
Serial Gateway
Mode
Server - Module will wait for a connection to be initiated by a remote Client.
Character
Timeout
Enter the maximum delay (in msec) between received serial characters before
packet is sent via network.
Packet Size
The number of received bytes that will be buffered before a packet is sent via the
network.
Listen Port
(Server)
Server Only. Enter the TCP port number on which the server must listen for
incoming connections. The standard TELNET port is 23.
Serial Gateway
Mode
Client - Module will automatically attempt to connect to the specified remote
server.
Character
Timeout
Enter the maximum delay (in msec) between received serial characters before
packet is sent via network.
Packet Size
The number of received bytes that will be buffered before a packet is sent via the
network.
Remote Device
Port (Client)
Client only. Enter the TCP port number of the remote server (i.e. the remote port
to automatically connect to).
Remote Device
IP Address
Client only. Enter the IP Address of the remote server.
Serial Gateway
Mode
Multicast - Allows point to multi-point serial transfer. All members of the group will
receive serial transmissions made by any other member of the Multicast group.