beautypg.com

Sensaphone 1800 User Manual

Page 40

background image

Sensaphone

1800 Manual

38

CONFIGURE TABLE RANGE FOR 4–20mA SENSORS

The 1800 allows you to create a unique linear table for each
4–20mA sensor Zone. The Table Low (4mA) and Table High
(20mA) values are used to define the upper and lower range of your
4–20mA sensor. For example, suppose you are using a 4–20mA
transducer to measure the depth of water in a 15 foot well. Simply
enter a Table Low value of 0 and a Table High value of 15 and the
1800 will scale the Zone to read between 0 and 15. The low and
high table range can be set from -10,000 to + 10,000. To make a
value negative, precede the value with the [RINGS/TAD/*] key.

To configure the Table Low and High Range:

1. Press the SET key.

2. Press the TABLE RANGE key.

3. Press the corresponding Zone number (1–8). 1800 will say

“Enter Low Number.”