beautypg.com

Sensaphone 1800 User Manual

Page 108

background image

Sensaphone

1800 Manual

106

APPENDIX A: Checking Your 1800 for Proper

Operation

We recommend that you test your 1800 weekly to be sure it
is functioning properly. This will ensure that when a problem
arises the 1800 will be ready to alert the appropriate personnel.
Phonetics, Inc. also recommends you keep a log of performed tests,
and has provided you with a Test Log template at the back of this
manual.

There are several tests that can be performed:

1. Call the unit and listen to the Status Report. This will test

the unit's ability to answer the phone and speak a message. It
will also verify that the inputs are reading properly, the alarm
conditions are OK, the electricity is on, the microphone is
functioning, and that the batteries are OK.

2. Create a test alarm on each input and allow the unit to contact

all programmed telephone numbers. This will make sure that the
1800 is programmed properly. It will also prepare personnel to
respond appropriately when they receive a call from the 1800.
Listed below are suggestions on how to trip test alarms:

• Temperature sensors: Heat or cool the sensor.

• Motion sensors: Have someone walk in front of the sensor.

• Door/window sensors: open the door/window.

• Water sensors: Apply a small amount of water beneath the

sensor or use a wet towel and touch it to the sensor probes.

• Humidity sensors: Raise the humidity around the sensor by

holding a cup of very hot water beneath the sensor.

• NO/NC Contacts: Open or close the contact.

Allow the unit to contact all programmed telephone numbers. This
will make sure that the 1800 is programmed properly. It will also
prepare personnel to respond appropriately when they receive a call
from the 1800.

3. Test the batteries by unplugging the AC adapter and making

sure that the 1800 continues to function. Press WHAT IS,