beautypg.com

Alarm programming, Appendix f: key sequence reference 125 – Sensaphone 1800 User Manual

Page 127

background image

Appendix F: Key Sequence Reference

125

Callback Acknowledgment Allows alarm acknowledgment with 10 rings

[SENSOR ON/OFF] + [CODE]

On or Off Default=Disabled (off)

Tone or Pulse Dialing

Dialing method—touch-tone or pulse

[SENSOR ON/OFF] + [PHONE NUMBER T/P]

On=Tone, Off=Pulse Default=Tone

Alarm Programming

Temp Alarm Limits

High and low temperature alarm limits

[SET] or [WHAT IS] + [LOW LIMIT] or [HIGH LIMIT]+[zone #]

2 .8K= Min:-109°F/-85°C Max:115°F/57°C

10K= Min:-87°F/-66°C Max:168°F/76°C

Default=Low: 0°F; High:100°F

4–20mA Table Range

Defines upper and lower range of 4–20mA sensor

[SET] or [WHAT IS] + [TABLE RANGE] + [zone #]

Min: -10,000, Max: 10,000 Default=Low: 0, High:100

4–20mA Alarm Limits

High and low alarm limits

[SET] or [WHAT IS] + [LOW LIMIT] or [HIGH LIMIT] + [zone #]

Min: -10,000, Max: 10,000 Default=Low: 0, High: 100

Zone Calibrate

Offset correction factor [temp/4-20mA]

[SET] or [WHAT IS] + [CALIBRATE] + [zone #]

Min: -15°/-100, Max: 15°/100 Default=0

Auto. Zone Configuration

Automatically configures all zones .

[SET] + [STATUS/CONFIGURE]

Default=n/a

Manual Zone Configuration To configure an individual zone type (required for 10K Temp)

[SENSOR ON/OFF] + [TABLE RANGE] + [zone #] + [type]

1 = NC, 2 = NO, 3 = 10K Temp, 4 = 4–20mA 6 = 2 .8K Temp

Default=n/a

Recognition Time Zones 1–8 Length of time a fault condition must exist to trip an alarm

[SET] or [WHAT IS] + [REC TIME] + [zone #]

Min:00:00, Max: 272:00 Default=00:03 (min:sec)

Rec Time: Power Failure

Length of time the power must be off to trip an alarm

[SET] or [WHAT IS] + [REC TIME] + [POWER]

Min: 00:00, Max: 272:00 Default=05:00 (min:sec)

Rec Time: High Sound Level Length of time the sound must be high to trip an alarm

[SET] or [WHAT IS] + [REC TIME] + [SOUND]

Min: 00:05, Max: 00:60 Default=00:08 (min:sec)

Sound Level Alarm Sensitivity Microphone sensitivity for high noise level alarm

[SET] or [WHAT IS] + [CALIBRATE] + [SOUND]

Min: 1 (most), Max: 255 (least) Default=32

Enable/Disable Zone

Turns zone alarm detection on or off

[SENSOR ON/OFF] + [zone #]