2 program blocks used, 3 symbolic variable names, Program blocks used – Lenze Drive Server Bus server S7 getting started User Manual
Page 56: Symbolic variable names, Busserver s7

Busserver S7
L
117
Busserver S7 DE/EN 1.0
6.6.2
Program blocks used
The project folder
Blocks contains the following program blocks:
Block
Function
OB1
Organisation block (program cycle); used to call
FC1
FC1
Siemens FC block
DP_SEND
FC2
Siemens FC block
DP_RECV
FC3
Function 3; used to call all other blocks
FB91
Function block
FB DRIVE CPenables parameter access via OPC and from the PLC
FC90
Function
FC Parameter for parameter data jobs from the PLC
FC93/FC94
Function for DP Process Data (3 words/2 words)
DB80
Data block
DB OPC for data exchange between OPC and FB90
DB81
Data block
DB S7PAR for data exchange between FC90 and FB90
DB30/31
Data blocks for data exchange between CPU and external communication processor (based on
UDT93)
DB90/100
Instance data blocks for
FB91
SFC57/SFC58
System blocks for communication via PROFIBUS-DP
UDT90 -
UDT93
Universal data types for parameter data access to Lenze drive controllers
VAT4
Variables table for changing the example parameters
6.6.3
Symbolic variable names
The same symbolic variable names are used as in the previously described example project ”S7-400”.
(
We recommend the use of symbolic variable names for clarity. However, they are not compulsory.