Busserver s7 – Lenze Drive Server Bus server S7 getting started User Manual
Page 42

Busserver S7
L
103
Busserver S7 DE/EN 1.0
Possible values/meaning
Data type
Parameters
R_Value
OUT: DINT
Read value (FIX32)
R_Value
OUT: DINT
If Status= 0x83, an I/O error occurred:
F0 F0 F0 F0 Module does not exist or SFC is not available
(decimal: -252 645 136)
F1 F1 F1 F1 Data length <> 8 bytes
(decimal: -235 802 127)
FF FF FF FF Other I/O error
(decimal: -1)
If Status = 0x80, the drive controller indicated an error.
•
Additional error codes and further explanations can be found in the
descriptions for the individual PROFIBUS interface modules.
06 03 00 00 No access permission
06 05 00 10 Unpermissible job parameter
06 05 00 11 Invalid sub-index
06 05 00 12 Data length too long
06 07 00 00 Object does not exist
06 08 00 00 Data types do not correspond
08 00 00 20 Job cannot be executed at present
08 00 00 21 Cannot be executed because of local control
08 00 00 22 Cannot be executed because of operating state of device
08 00 00 30 Value range has been exceeded
08 00 00 40 Collision with other values
Trigger
INOUT: BOOL
TRUE Start job processing.
•
Automatically reset to FALSE, when the job has been
completely processed and the result is available.
Show/Hide Bookmarks