2 Instrument Description
2.5.6
Recording period of the counts
For all counters, integrators, operating time counters, and high-speed
counters, the counters are concluded and the counter states are stored and
restarted after an adjustable amount of time (recording time period). The
counter states of the most recently completed recording period can be
numerically displayed.
The following counter/integrator types are possible:
• Periodic
In addition, the time period (from 1 min to 12 hrs)must be selected in the
parameter Configuration
Counters/Integrators
General settings
Period.
• External
In this case, the counter/integrator is updated only when the selected
control signal is active (e.g. binary input is closed). When the control signal
is deactivated (e.g. binary input is opened), the counter/integrator value is
saved and reset to 0.
• Daily
• Weekly
• Monthly
• Yearly
• Total
• Daily (start — end)
In addition, the time period must be selected through the two parameters
Configuration
Counters/Integrators
General settings
Start and
Configuration
Counters/Integrators
General settings
End. The
counter/integrator will then only be updated from the start time. When the
end time has been reached, the counter/integrator value is saved and then
reset to 0.