21 Configuration - Counters/Integrators

21.3 Input Signal … Decimal Place

Overview

Input signal

Input signal which will be counted or integrated. If High-speed counter or Flow
rate quantity
was selected for the Function setting, Input signal is not
available. The assignment cannot be changed.

Weighting
(evaluation)

For binary signals (counter), each time the signal is set, the result is increased
by the Weighting factor. With analog signals (integrator), the current measuring
value is multiplied by the Weighting and added to the result.
A down-counter can be formed by a negative weighting. Weighting is not
available for the Function “Operating time”.

Time base

With the Integrator function, the current measurement value (with weighting
factored in) is integrated according to the time base.

With the Operating time function, the time base determines the unit of
measure of the operating time counter.

Second

The measurement is divided by 1 and totalized every
second.

Minute

The measurement is divided by 60 and totalized every
second.

Hour

The measurement is divided by 3600 and totalized every
second.

Day

The measurement is divided by 86400 and totalized
every second.

Second

The operating time is shown in seconds.

Minute

The operating time is shown in minutes.

Hour

The operating time is shown in hours.

Day

The operating time is shown in days.