19 Configuration - Report
146
Synchronization
time
Synchronization time is used for the daily, weekly and periodic report, for the
report end and restart.
The parameter Synchronization time is explained below, using a period report
as an example.
Stop and restart will occur at the next instant of time which fits into the time
grid, dependent on the Synchronization time and Period.
Example:
Period
= 2 hours
Synchronization time
= 11:30:00
Power ON
= 09:11:00
1. Period 1 from 09:11 to 09:30 = 19 minutes
2. Period from 09:30 to 11:30 = 2 hours
3. Period 3 from 11:30 to 13:30 = 2 hours
etc.
Out of range
„Out of range“ determines what happens when an internal or external analog
input, or an allocated math channel, is outside the valid measurement range
(scaling).
H
The principle is identical for all reports that are dependent on the
Synchronization time (daily, weekly and periodic report).
As a rule, in the case of the daily report, the first report will not be
run for 24 hours, and, in case of the weekly report, not for 7 days.
Stop
The channel reports are stopped. When the
measurements are within the range limits again, they will
continue to be run.
Delete
The reports are set to invalid (“-----”) and will be
restarted only after the configured report end has
elapsed.