Operating Instructions Safety System MGB-L..B-PN.-... (PROFINET)

9

Case B

You have an MGB with a version number of V 2.36.4 and a GSD file with a version

number of ..._110026-20110725 or older.
The guard locking solenoid is controlled if
for MGB-L1...

Ìbit SO 0.0 = 1

for MGB-L2...

Ìbit O 0.0 OR bit SO 0.0 = 1

Truth table:

PROFINET bit

PROFIsafe bit

Guard locking with

O 0.0

SO 0.0

MGB-L1...

MGB-L2...

0

0

active

inactive

0

1

inactive

active

1

0

active

active

1

1

inactive

active

What must be observed?
Bit O 0.0 does not have any function with version MGB-L1.... In existing installations

in which old devices are replaced with new ones (e.g. due to defect), malfunctions

can occur if control via bit O 0.0 was programmed in the PLC.
Remedy:
1. Replace the old GSD file with a version from ..._110026-20110815.
2. In the parameter Locking module – solenoid control, activate unsafe control

of the guard locking solenoid via bit O 0.0.

3. Set bit SO 0.0 permanently to the value 1.

¨

The guard locking solenoid is controlled exclusively via bit O 0.0

or

Ìchange the control bit from O 0.0 to SO 0.0 in your PLC program.