Operating Instructions Safety System MGB-L..B-PN.-... (PROFINET)

24

Setup

Integrating into PROFINET and PROFIsafe

Attention:

The parameters "Update time" and "F-WD-Time" have a decisive effect on the
reaction time of the safety function. The safety function could be lost if the reac-
tion times are too long.

Important!

You will require the corresponding GSD file in GSDML format in order to integrate
the MGB system:

ÌGSDML-Vx.x-EUCHNER-MGB_110026-YYYYMMDD.xml

You can find the GSD file in the download area at www.EUCHNER.de.

Prior to commissioning, the GSD file must be imported into the configuration
software for the control system (see control system manual).

You must perform the following steps to integrate the MGB system into PROFINET:
1. Configure the MGB system with the configuration software of the control

system and assign parameters.

The following PROFINET parameters must be set:

ÌDevice name (factory setting from GSD file): [euchnermgb].
ÌIPaddress: optionally fixed or dynamic
ÌUpdate time

Recommendation [32 ms]

Maximum value [128 ms]

(with number of repeat cycles = 3)

The following PROFIsafe parameters must be set:

ÌF_dest_adr (PROFIsafe address): this is generally assigned automatically by the

control system.

ÌF_WD_Time (time during which the control system expects a response by the

PROFIsafe device): [xxx ms]. Factory setting from GSD file: (600 ms)

2. Set the PROFIsafe address (F_dest_adr) on the MGB system using the DIP-

switches (see Figure 16). Important: Identical addresses must be set in the

control system and on the device.

3. Save the configuration and transfer it to the MGB system.