beautypg.com

Det-Tronics R7495D UV/IR Flame Detection System User Manual

Page 19

background image

STAR Logic Programming (System Sensitivity and
Time Delay) - Rocker Switches 2-1 to 2-8 (Gate
Length), Rocker Switches 3-1 to 3-4 (Count Selection
Per Gate), and Rocker Switches 3-5 to 3-8
(Consecutive Gates Selection).

The STAR Logic switch settings determine system sen-
sitivity and time delay. The most important factor in
determining the appropriate sensitivity setting for a par-
ticular application is the intensity of radiation expected
to reach the detector in the event of a fire. This
depends on several factors, including the distance of
the detector from the potential fire, the fuel type, the
flame size, and whether any radiation absorbing vapors
are present (these are listed in Table 2).

The most effective way to set system sensitivity is to
install the system, program the STAR Logic according
to the typical settings shown in Figure 21, program all
other aspects of controller operation according to this
section (“Programming the Controller”), then perform
the “Initial and Periodic Checkout Procedure” using a
UV/IR test lamp and the “STAR Programming Checkout
Procedure.” If the system fails to respond appropriately
during these tests and all system wiring is correct, then
system sensitivity (gate length, counts per gate, and
consecutive gates) needs to be adjusted. It is important
that all wiring and programmed settings be checked to
ensure that they are correct before adjusting these set-
tings.

Rocker switch assemblies 2 and 3 control three variables:
gate length, counts per gate and consecutive gates
required for a fire output. Refer to Figure 21 for a visual

representation of how these variables function together
with typical controller settings. Keep in mind that when
the UV and IR sensors of the detector respond to a fire,
the IR sensor activates the circuitry in the UV/IR detector
junction box. This allows the electrical pulses (signal)
from the UV sensor to be sent to the controller. The fre-
quency of this signal is proportional to the intensity of the
fire. The controller looks at this signal in comparison to
the sensitivity settings in order to determine whether a fire
exists. A brief description of each variable follows:

1. Gate Length is adjustable from 31.25 milliseconds

to 8 seconds. The gate length is the increment of
time that the controller looks at the detector signal
to determine if the “Counts per Gate” requirement is
fulfilled. In Figure 21, the gate length is 0.25 sec-
onds (Rocker Switch 2-4 closed, Rocker Switches
2-1, 2-2, 2-3, 2-5, 2-6, 2-7, and 2-8 open).

2. Counts per Gate is adjustable from 2 to 15 counts.

These counts make up the signal from the detector
and are a direct response to a flame or other UV/IR
source. In Figure 21, the counts per gate setting is
4 counts (Rocker Switch 3-3 closed, Rocker
Switches 3-1, 3-2, and 3-4 open).

3. Consecutive Gates required for a fire output are

adjustable from 2 to 15 gates. This is the number of
consecutive gates in which the “Counts per Gate”
requirement is fulfilled that the controller must see
before going into a fire alarm condition. In Figure
21, the consecutive gates setting is 4 gates (Rocker
Switch 3-7 closed, Rocker Switches 3-5, 3-6, and 3-
8 open).

19

95-8331

Figure 20—Rocker Switch Setting

B1053

SWITCH ASSEMBLY 3

COUNT SELECTION

CLOSE ROCKERS TO ACTIVATE

ROCKER 1 – 1 COUNT

ROCKER 2 – 2 COUNTS
ROCKER 3 – 4 COUNTS
ROCKER 4 – 8 COUNTS

VALUES OF ROCKERS CLOSED

ARE ADDED TOGETHER – 2 COUNTS MINIMUM

IF GATE IS GREATER THAN OR EQUAL

TO 0.5 SECOND, A MULTIPLICATION FACTOR

MUST BE USED.

CONSECUTIVE GATE SELECTION

CLOSE ROCKERS TO ACTIVATE

ROCKER 5 – 1 GATE

ROCKER 6 – 2 GATES
ROCKER 7 – 4 GATES
ROCKER 8 – 8 GATES

VALUES OF ROCKERS CLOSED

ARE ADDED TOGETHER – 2 GATES MINIMUM

SWITCH ASSEMBLY 2

GATE LENGTH

CLOSE ROCKERS TO ACTIVATE

VALUES OF ROCKERS CLOSED

ARE ADDED TOGETHER

ROCKER SWITCH NUMBERS ARE DESIGNATED 1-1, 1-2, 1-3, ETC.
THE NUMBER PRECEDING THE DASH INDICATES THE SWITCH ASSEMBLY.
THE NUMBER FOLLOWING THE DASH INDICATES THE ROCKER NUMBER.

NOTE 1:

DEPRESS ROCKER TOWARD "OPEN" ON SWITCH ASSEMBLY TO SET IN THE OPEN POSITION.
DEPRESS ROCKER TOWARD NUMBER DESIGNATIONS TO SET IN CLOSED POSITION.

NOTE 2:

SWITCH ASSEMBLY 4

FIRE ZONES

ROCKER 1 –

INDIVIDUAL RESPONSE

WHEN ROCKER IS CLOSED,

COMBINED WHEN ROCKER IS OPEN.

OUTPUTS LATCHING

ROCKER 5 –

LATCHING OUTPUTS WHEN ROCKER IS OPEN

ROCKERS 2 AND 6 NOT USED

SWITCH ASSEMBLY 1

DETECTOR SELECTION SWITCH

PLACE ROCKER IN OPEN POSITION

FOR EACH CHANNEL WITH A DETECTOR CONNECTED

ROCKER 1 – 31.25 MILLISECONDS
ROCKER 2 – 62.5 MILLISECONDS
ROCKER 3 – 0.125 SECOND
ROCKER 4 – 0.25 SECOND
ROCKER 5 – 0.5 SECOND
ROCKER 6 – 1 SECOND
ROCKER 7 – 2 SECONDS
ROCKER 8 – 4 SECONDS