beautypg.com

Aerovent IM-500 User Manual

Page 9

background image

9

Aerovent IM-500

Flame Safeguard Control

(Aerovent Part #25941-01)

All units are equipped with a Honeywell RM7895C flame

safety relay. This relay senses if a pilot flame and main

burner flame have been established through the use of an

ultraviolet (UV) scanner. For more information about the

Honeywell flame relay, visit the Honeywell web site.

The flame safeguard relay has a built in component self

checking module, pre-purge timer, and an ignition timing

flame sensing circuit. The pre-purge timer allows purg-

ing of any residual gas or fumes in the unit before a try

for ignition. Pre-purge is approximately 10 seconds. After

pre-purge occurs, the spark ignition will start. If the pilot

flame is not proven within the time period allowed (10 to

25 seconds) the relay will go into lockout and it will have

to be manually reset before a try for re-ignition can occur.

This can be accomplished by pressing the reset button on

the remote station or at the unit thus preventing a trip to

the air make-up unit. If after several (2-3) tries the unit

won’t light off, have a maintenance man inspect the unit to

determine cause of relay lockout.

Note: The power light

will blink; this is a normal operating condition.

C7027 Ultra Violet Scanners

(Aerovent Part #2281-01E)

Units are equipped with a C7027A UV scanner. This device

is shipped removed from the flame sighting tube to prevent

damage during shipment. Unwrap the device and mount

on the sighting tube. The UV scanner is a ultra-violet light

sensing device. It takes advantage of the fact that a flame

will emit some of its light in the low frequency ultra violet

light range. The scanner uses an electronic eye to scan for

the presence of this ultra violet light. If flame is detected,

it sends this signal to the RM7895C flame relay.

Gas Pipe Train Configuration

(Aerovent Part #2281-01E)

The type of manifold supplied with the unit varies depend-

ing on whether the unit was ordered with a FM or IRI

manifold. To determine which arrangement was supplied

with the unit, see the manifold descriptions noted on the

product specification and general description page in the

front of this manual.

Pilot Solenoid Gas Valve

(Aerovent Part #422-05E)

The pilot solenoid gas valve serves as a separate shut-off

valve for the pilot gas during normal operation and pro-

vides means for interrupted pilot and main flame supervi-

sion during normal operation of the unit.

Figure 7. FM Piping

Figure 8. IRI Piping

Figure 9. Pilot Valve

Figure 5. Flame Relay

Figure 6. UV Flame Detector (Purple Peeper)