beautypg.com

Aerovent IM-500 User Manual

Page 16

background image

16

Aerovent IM-500

Remote Switch in “Summer” Position

With the remote switch in the “Summer” position, the fol-

lowing sequence of operation will occur.

1. Inlet and/or discharge damper is energized.

2. When damper is 65% open, the internal damper motor

end switch will make and allow power to be supplied to

the motor or motor starter. Fan will start and supply air

to the distribution system. The blower light will come

on.

3. The gas controls and temperature controls are locked

out to prevent heating during the “Summer” mode.

Note: The burner will not come on with the switch in

“Summer”. The fan will continue to run as the temperature

drops.

Remote Switch in “Winter” Position

If freeze protection is furnished with the unit, the freeze

protection timer will be energized at this time to provide

power to the inlet and/or discharge damper.

With the remote switch in the “Winter” position, the

above sequence continues:

4. The running interlocks supply power to the flame relay

through contacts on high temperature limit control and

high and low gas pressure switches, mild weather tem-

perature stat, proof of airflow switch, proof of closure

switch and freeze protection sensor.

5. After 7 seconds of pre-purge time, the flame safeguard

ignition sequence is energized, the ignition transformer

is energized and pilot valve is opened.

6. After pilot is lit and proven, the main gas valves are ener-

gized and the burner fires at low fire. The burner “On”

light is energized on the remote panel when the main

valves are completely open and the end switch is made.

7. Burner remains on low fire until the main valves are

100% open and the end switch is made. The tempera-

ture controls then take over and modulate burner firing

based on load demands.

NOTE: If the unit has been supplied with a dirty filter

switch, the filter light will come on if the pressure drop

across the filters becomes excessive.

If a flame failure should occur (lock out time: 17 sec-

onds) the burner light on the remote panel will go out. The

flame safeguard relay will go into lockout. The unit selector

switch must be turned off before the unit can be restarted

again. The flame safeguard reset button (optionally located

on the remote station) must be manually reset in order to

restart the burner. If you have a remote reset, travel to the

unit is not required.

CAUTION:

After resetting the reset button on the flame safeguard

relay three times and the unit fails to light off, have service

department check unit to determine cause of failure.

Using the Circuit Analyzer to

Isolate Defective Components

Troubleshooting the Aerovent air make-up control systems

has been simplified by the use of the circuit analyzer. The

light numbers are the same as the wire numbers for each

circuit. They are also arranged to operate in sequence. The

analyzer is turned on by the toggle switch. If any circuit is

not energized, the sequence will stop at that point until the

fan shuts down (approximately 90 seconds). It should be

emphasized that the circuit analyzer will show the location

of a malfunction only during the starting cycle. To start

a new cycle, turn the unit off, wait 30 seconds, and then

turn it on again. Observations are made with the discon-

nect switch closed and the selector switch in the “Winter”

position.

If lamp #3 does not light, check:

1. Is lamp #3 getting power or is the bulb defective?

2. The fuse (Buss FNM 5 amp).

3. Line voltage on the primary side of control transformer.

4. Control voltage on secondary side of control trans-

former.

5. Jumper between H and 1 on the terminal strip.

6. Continuity between 1 and 3 on the selector switch.

If lamp #4 does not light, check:

NOTE: May not come on until flame is established.

1. Is lamp #4 getting power or is the bulb defective?

2. Contacts and operation of low temperature limit ther-

mostat (Dial setting 30

o

). Temp. below setpoint.

If lamp #5 does not light, check:

1. Is lamp #5 getting power or is the bulb defective?

2. Contacts and operation of reset timer.

If lamp #6 does not light, check:

1. Is lamp #6 getting power or is the bulb defective?

2. Operation of shutter motor.

If lamp #7 does not light, check:

1. Is lamp #7 getting power or is the bulb defective?

2. Contacts and setting of mild weather thermostat.

3. Ambient temp above MW setting.

If lamp #8 does not light, check:

1. Is lamp #8 getting power or is the bulb defective?

2. Selector in “summer” position.

3. Continuity between 7 and 8 on the selector switch.

If lamp #9 does not light, check:

1. Is lamp #9 getting power or is the bulb defective?

2. Line gas pressure.

3. Low gas pressure switch. (Manual reset)

If lamp #10 does not light, check:

1. Is lamp #10 getting power or is the bulb defective?

2. High gas pressure switch. (Manual reset)