beautypg.com

Aerovent IM-500 User Manual

Page 18

background image

18

Aerovent IM-500

LUBRICATION INSTRUCTIONS FOR FANS AND

BLOWERS

Bearings and grease lines on fans are lubricated on assembly.

When lubrication is required, add grease slowly while shaft

is rotating until grease comes rapidly out of the relief port

on the fitting. For extreme conditions lubricate according

to experience. Check lubrication table in Aerovent IM-100

for frequency recommendations.

LUBRICATING DOOR HINGES

Door hinges should be lubricated on a monthly basis even

though they are stainless steel to keep hinges from “freez-

ing up” due to lack of use. Apply oil at the hinge and work

the oil in by opening and closing the door several times.

LUBRICATION INSTRUCTIONS FOR MOTOR

Grease lubricated bearings as furnished are adequate for

a long period of operation without relubrication. A good

maintenance schedule for regreasing will vary depending

on motor size, speed, duty and environment. See lubrica-

tion table in IM-100.

The table suggests relubrication intervals for motors on

normal, steady running, light duty indoor loads in relatively

clean atmosphere at 40

o

C (105

o

F) ambient temperature

or less. Motors with no provision for lubrication are

equipped with sealed bearings and require no maintenance.

Motors mounted in inaccessible locations are provided

with extended grease lines to facilitate lubrication. They

are equipped with relief fittings to prevent overlubrication.

The grease lines are filled with lubricant at the factory.

SERVICE INSTRUCTIONS FOR FILTERS

If the unit is supplied with a dirty filter switch and light,

clean or replace the filters any time the dirty filter light

comes on.

Units which do not have a dirty filter warning light

should have the filters checked monthly. Clean or replace

if necessary. In dirty atmospheres, filter maintenance may

be required more often.

SERVICE INSTRUCTIONS FOR BURNERS

Generally, direct-fired burners tend to be self cleaning,

however, if the unit is installed in a severely dirty environ-

ment a periodic cleaning of the burner may be required.

Depending on the size of the burner it may not be prac-

tical to attempt to remove the burner from the unit. The

burner can still be cleaned by using the following steps:

1. Turn off gas and power. Remove the pilot and igniter

assembly from burner.

2. Break the gas union at the burner and isolate the burner

piping from the manifold piping.

3. Seal the open end of the manifold piping with duct tape

or other means to prevent dirt from entering the mani-

fold pipe and/or gas controls.

4. Using a high pressure air hose (40 to 80 psi) flush the

burner gas ports from the flame side of the burner.

Continue flushing until dust particles are removed.

NOTE: If air pressure alone is not sufficient to clean the

burner gas ports, the ports may be cleaned by using the

appropriately sized drill from a numbered drill set. Consult

Maxon literature at www.maxoncorp.com for the proper

bit. NP-LE burners require different bits than that of an

NP (#47). See Figure 20.

When using a drill to clean the burner gas ports, be

careful not to distort or enlarge the ports.

5. Examine the stainless steel mixing plates carefully.

They should be clean and not warped or cracked. It

is especially important to make sure the mixing plates

nearest to the burner manifold are clear. Mixing plates

can be cleaned with compressed air or wire brush.

6. Remove the protective cover, which was placed on the

manifold piping in Step 3, and reconnect the gas union.

7. Reassemble pilot and igniter assembly to the burner.

8. After cleaning and reassembly, use a soap/water solu-

tion to check for gas leaks in the piping.

9. Restore power and gas to the unit. Reset pressure

switches.

10. Run the fan in the “Summer” position to see that the

damper is opening and closing properly. Be sure that

the gas is on and the proper pressure is indicated. Turn

the unit on in the “Winter” position and observe its

operation on the circuit analyzer. (If it is a warm day,

it will be necessary to increase the setting of the mild

weather thermostat in order to get the unit to fire.)

Watch the burner when it first lights. It should light off

with a low flame, then increase in size and stabilize out

somewhere in between. This would indicate that the

modulating system is working.

11. If you have cleaned the burner plates or if the burner

plates are dusty, there will be a lot of color in the flame

and luminous particles will be present. These will dis-

appear after the burner operates for a while.

If the unit fails to operate, refer to the section on trouble

shooting and analyze the problem. After you are satisfied

with the checkout, be sure to set the mild weather control to

the desired heat-off temperature. This is usually 60

o

to 65

o

.

GAS AND ELECTRIC CONTROLS

Inspect for general cleanliness and tightness of electric and

mechanical connections. Check gas valves a minimum of

once per year for tightness of the safety shut-off valves

using the leak test ports on the valves

*** CAUTION ***

KNOW WHICH BURNER

YOU HAVE PRIOR TO DRILLING