beautypg.com

Annual maintenance recommendations – Aerovent IM-500 User Manual

Page 17

background image

17

Aerovent IM-500

If lamp #11 does not light, check:

1. Is lamp #11 getting power or is the bulb defective?

2. High temperature limit thermostat. (Manual reset)

3. Not properly set.

If lamp #12 does not light, check:

1. Is lamp #12 getting power or is the bulb defective?

2. Airflow switch adjustment

3. Dirty filters or loose belts.

If lamps #13 & #14 do not light, check:

1. Are lamps #13 and #14 getting power or are the bulbs

defective?

2. Reset button on the RM7890 flame relay.

3. Connection of the wire #13 to terminal 10 on the flame

relay and wire #14 to terminal 8.

4. C7027A flame sensor. Remove from the sighting tube

and observe UV tube during new sequence. If it lights

(bright orange) or flickers when fan starts, it is defective.

(Replace) It should flicker when it sees a flame. If it

glows solid, replace.

5. If it does not flicker occasionally or light, replace the

RM7890.

NOTE: #13 and #14 come on at the same time. #13 will

go out after flame is proven. #14 will stay on for the ten

second flame establishing period. #15 is energized when

#13 is turned off.

If lamp #15 does not light, check:

1. Is lamp #15 getting power or is the bulb defective?

2. Are the valves opening and staying open?

3. Is the flame light on the flame relay coming on? The

flame being proven during PFEP.

4. See check out procedure for C7027A sensor under #13

& #14.

If lamp #16 does not light, check:

1. Is lamp #16 getting power or is the bulb defective?

2. Operation of safety shut-off valve.

3. Auxiliary switch in the safety shut-off valve.

NOTE: If all lights come on for approximately one minute,

then #14, #15, and #16 go out, followed by a shutdown

in 15 seconds, check flow of gas through valves to burner,

and also burner port openings.

When unit has been checked, turn the circuit analyzer off.

These are 20,000 hour neon lamps and should last the life

of the equipment, unless the analyzer is left on after use.

NUISANCE SHUTDOWNS

Occasionally the unit may shut down during normal opera-

tion. Simply by turning the selector switch to the “off ”

position for 30 seconds, then back to “Winter”, the unit will

start again through a complete cycle and run normally. This

condition could be caused by one of the following:

1. Momentary Loss of Power

2. Low Temperature Limit

3. Airflow Switch

EXAMPLE: Low limit opens during operation or remains

open on initial start up due to insufficient heat. Manually

reset the unit by turning the selector switch to “OFF”, then

back “ON”. All other controls will require manual reset at

the control, except the airflow switch.

Notes:

Usually nuisance shut downs are one of two things:

a) Low temperature limit: The unit shuts down as soon as

the reset timer times out.

b) Air Flow Switch: Typically these are periodic shut downs

and do not happen predictably.

FOR TROUBLE SHOOTING TEMPERATURE

CONTROLS CONSULT THE MAXITROL

BULLETIN FOUND AT WWW.MAXITROL.COM.

Annual Maintenance

Recommendations

MAINTENANCE SCHEDULING

Prior to heating season each year, the following inspections

and tests should be made to be sure the unit is in proper

operating condition for the heating season.

Turn off power at the main disconnect switch. Examine

the inside of the air make-up unit. See that the thermostat

and temperature sensing elements are in place and their

support brackets are solid. Examine the damper blades and

linkage to insure that they have not been damaged. Turn

the propeller by hand to be sure the bearings turn freely

with no rough spots or noise. Be sure the grease lines and

fittings are intact. Check the velocity monitor to be sure

the venturi and the tubing to the airflow switch are not

obstructed.

BLOWER ASSEMBLY

The blower assembly includes the fan bearings, drive

sheaves and belts.

Bearings should be checked for any unusual wear and

replaced if needed. Also make sure bearings are secure and

locking collars tight.

Check the belt drive for proper tightness and align-

ment. If belts are beginning to wear, replace them. If the

sheaves show signs of wear in the grooves, replace both

fan and motor sheaves and the belts.

(New belts should

be retightened after 24 hours of operating and

again after a week’s operation.)