beautypg.com

Electrical connections, Gas piping installation – Aerovent IM-500 User Manual

Page 6

background image

6

Aerovent IM-500

required, as structural design of accessories

will support these items. However, rails should

be extended to support cross members of the

accessories. Check the drawings in the front of

this manual.

Electrical Connections

CAUTION:

Disconnect power source before making wiring connec-

tions to prevent electrical shock and/or equipment damage.

WARNING:

ALL UNITS MUST BE WIRED STRICTLY IN

ACCORDANCE WITH THE WIRING DIAGRAM

FURNISHED WITH THE UNIT AND IN

ACCORDANCE WITH THE NATIONAL ELECTRIC

CODE ANSI/NFPA 70, LATEST EDITION. UNIT

MUST BE ELECTRICALLY GROUNDED IN

CONFORMANCE TO THIS CODE. ANY WIRING

DIFFERENT FROM WIRING DIAGRAM SUPPLIED

SHOULD BE CLEARED WITH FACTORY

ENGINEERING WITH WRITTEN APPROVAL FOR

VALIDATION OF UNIT WARRANTY.

Any damage to, or failure of this equipment caused by

incorrect wiring of the unit is not covered under the stan-

dard product warranty.

Electrical wiring diagrams are furnished with each unit

and can be found in the O&M manual, and a permanent

laminated diagram is located on the inside of the electric

control cabinet door. All units are supplied with a labeled

terminal strip for ease of wiring.

The power supply to the standard unit is be protected

with a lockable type fused disconnect switch. If a discon-

nect switch is not supplied with the unit, the field supplied

disconnect must have adequate ampacity and must be

installed in accordance with Article 430 of the National

Electrical Code, ANSI/NFPA 70.

External electrical service connections which must be

made include:

1. Main power supply to unit (120, 208, 240, 480, or 575

volt).

2. Remote control panel. Consult unit wiring diagram.

3. Separate 120V service for lighting and receptacles as

required.

4. Control wires connected to the remote temperature

selector must not be run close to or inside conduit with

power or ignition wires. Doing so may cause the unit

to function erratically or may destroy the amplifier. If

shielded wires are used, shield must be insulated and

grounded at the amplifier location only.

Supply voltage must be within 10 percent of the power rat-

ing with each phase balanced to within 2 percent of each

other. If not, advise the power company.

Before powering unit, make sure all multi-

voltage components (transformers, motors, etc.)

are wired in accordance with the correct supply

voltage.

The lighting circuits and unit receptacles

require the installation contractor to supply a

separate 120 volt single supply source to the

unit and be installed in accordance with Article

210 of the National Electrical Code ANSI/NFPA

70 - 1987.

Gas Piping Installation

CAUTION:

Gas pressure to main gas manifold must NEVER

EXCEED 5 psi.

The unit and its individual shutoff valve(s) must

be disconnected from the gas supply during any

pressure testing of the piping system. Before

assembling piping to unit manifold contractor

should be sure all rust, piping compound and

shavings have been removed from new piping.

(Strainers are recommended between unit pipe

train and supply piping.)

Always check the unit’s data form to determine the cor-

rect gas supply pressure for which the unit was designed.

1. Installation of piping must be in accordance with local

codes, and ANSI Z223.1, latest edition, “National Fuel

Gas Code”. (In Canada CAN/CGA-B149 Code).

2. Piping to units must conform to local and national

requirements for type and volume of gas handled,

and pressure drop allowed in the line. Refer to the air

make-up data form to determine the Btu capacity of

the unit and the type of gas the unit is designed to use.

Using this information refer to the ASHRAE Guide

Fundamentals Handbook, or other gas pipe sizing

guide to determine the correct supply pipe size. Allow

sufficient pipe size based on allowable pressure drop

in supply line. Where several units are served by the

same main, the total capacity of all the units served by

the main must be used. Avoid pipe sizes smaller than

1

/

2

".

3. After threading and reaming the ends, inspect piping

and remove loose dirt and chips.

4. Support piping so that no strains are imposed on the

unit controls.

5. Use two wrenches when connecting field piping to

units.

6. Provide a drip pocket before each unit and in the line

where low spots cannot be avoided.

7. Take-off to unit should come from top or side of main

to avoid trapping condensate.

8. Piping subject to wide temperature variations should

be insulated.

9. Pitch piping at least

1

/

4

" per 15 feet of horizontal

run.

10. Compounds used on threaded joints of gas piping

must be resistant to action of liquefied petroleum

gases.