NOTE: RECOMMENDED FREQUENCY OF TEST IS

ONCE PER MONTH.

32. Safety shut off valve leak test. Remove cap from test

cock. Close the manual valve on the vent line. The

main S.S. and blocking valves are closed. Open the test

cock - check for gas leak. If no leak detected close test

cock and cap. Open the manual valve in the vent line.

33. Check gas input rate.

Actual input rate should be checked and necessary

adjustments made after the unit is installed. Over-firing, a

gas pressure result of too high an input, reduces the life of

the unit, increases maintenance, lowers burner efficiency

and can result in poor combustion. Under no circumstance

should the input exceed that shown on the unit specifica-

tion description.

The following procedure describes how the gas input

check is accomplished.

Pressure Method

The pressure method determines input by measuring the

pressure of the gas in the burner manifold in inches of

water. (Designed for 7 in. w.c. MAXIMUM.)

1. Close manual valve.

2. Remove the

1

/

8

" pipe plug test port at the burner and

attach water manometer of “U” tube, which is at least

12" high or pressure gauge calibration with a range of 0

to 15 in. w.c.

3. Open manual valve and start unit.

4. If pressure as indicated by “U” tube or gauge is not

more than

1

/

2

" higher or lower than 7 in. w.c. on the

system spec description, adjust the Maxitrol gas valve

regulator as per the vendor literature that is shipped with

the unit.

If pressure as indicated by “U” tube is more than

1

/

2

"

higher or lower than 7 in. w.c., check the inlet gas pressure

at unit. Adjust main gas regulator to supply the correct gas

inlet pressure as described on the unit’s system specification

description.

Multi-Speed Units

Units with two-speed motors or variable airflow options

require the following additional start-up checks.

Two-Speed Units

1. Check the motor and blower speed at both high and low

speed.

2. Check motor amps at both high and low speed.

Variable Airflow Units

50/50, 60/40, or 70/30 Options

1. Check to make sure that the outside air burner bypass

damper and return air damper operate correctly without

binding.

80/20 Building Pressure Control

1. Check that the outside air burner bypass damper and

return air damper operate correctly without binding.

2. Check to make sure building pressure control is operat-

ing correctly.

The building pressure control is designed to open the

outside air burner by-pass damper and close the return air

damper as the negative pressure in the building increases.

To check if this is occurring, turn on an exhaust fan

and observe the return air damper position. It should start

to close. Turn on additional exhaust fans. The return air

damper should close further.

With all of the exhaust fans running, the return air

damper should be in the fully closed position and the

burner by-pass damper should be in the fully open position.

Check and adjust as necessary.

After all the initial start-up procedures have been

performed, the unit is ready for commissioning. Set the

temperature controls for the recommended control safety

device settings:

1. High gas pressure switch set at 12 in. w.c.

2. Low gas pressure switch set at 2 in. w.c.

3. High temp thermostat 150

o

F

4. Low temp thermostat 40

o

F

5. Mild weather thermostat set at 65

o

F

6. Reset timer 3 min.

7. Room temp. Set point as desired.

8. Airflow switch approx. 2-3 turns from closed position.

9. Building pressure control 0.01 to 0.03 in. w.c.

If the unit is to be left for stand-by operation, set the

Summer/Off/Winter switch to the “Off ” position and

turn the electric power off at the unit’s disconnect switch.

NOTE:

LOSS OF WARRANTY OCCURS IF WARRANTY

START-UP REPORT IS NOT SUBMITTED TO

AEROVENT

Warranty Start-up Report

A Start-Up Report form is included in the back of this

manual. Before turning the unit over to the owner, make

sure the Start-Up Report has been completely filled out,

signed, and dated. Submit a copy of the start-up report

to Aerovent Company, 800 S. High St.., Covington, OH

45318. The fax number is (937) 473-3793.

Operating Sequence

Remote Switch in “Off” Position

With Summer/Off/Winter switch in the “Off ” position

the unit is shut down and either the blower or burner will

operate.